Exalt

Gas Valve Replacement 

4

Fig. 6:  Controls display

3.  Press the RIGHT button to highlight the Manual 

Operation icon then press the OK button.

4.  Press the center button while the FAN icon is high-

lighted to manually fire the burner and power the 

CH circulator. See Fig. 6

NOTICE

An adequate CH load must be present to dissipate the heat 

generated during the combustion test. If an adequate CH 

load is not available, an indirect water heater can be used to 

dissipate the heat by creating a DHW call which will enable 

the DHW circulator.

5.  Press the RIGHT button to adjust the firing rate to 

100% (high fire).  Hold down the  RIGHT button to 

rapidly increase the firing rate.

6.  If the combustion levels during high fire are outside 

the recommended combustion settings, adjust the 

THROTTLE SCREW using a flat-blade screwdriver as 

follows:

Counter-clockwise adjustment of the THROTTLE 
SCREW at High Fire (100% firing rate):

 

Increase CO2 & Decrease O2

Clockwise adjustment of the THROTTLE SCREW at 
High Fire (100% firing rate):

 

Decrease CO2 & Increase O2

7.  Once the combustion level is set at high fire, manu-

ally place the boiler into low fire mode by pressing 

the LEFT button to adjust firing rate down to 0% 

(low fire).

8.  If the combustion level (O2 or CO2) during low fire 

is not /-0.2 of the combustion level mea-

sured at high fire, shut down the boiler and contact 

ideal Tech Support at 1.800.411.9999

9.  Reattach the front jacket panel and return the unit 

to normal service. 