49
FAULT FINDING
FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING FAULT FINDING
combination boiler -
Installation and Servicing
NO
YES
IS THE DHW WATER TEMPERA-
TURE STABLE
IS THE WATER FLOW
CONSTANT AT APPROX
10 l/min
ENSURE THE WATER
PRESSURE IS
CONSTANT AND THE
SUPPLY IS STABLE
IS THE VOLTAGE Vdc AT
PLUG A2 BETWEEN PINS 3
AND 4 STABLE
REPLACE FAULTY PCB
IS THE BURNER
PRESSURE STABLE
REPLACE FAULTY GAS
VALVE
FAULTY THERMISTOR
(THIS HAS NOW BEEN
REPLACED)
IS THE DHW TEMPERATURE
SATISFACTORY
REPLACE FAULTY
THERMOSTATIC
ELEMENT IN 3 WAY
VALVE
RECTIFY EXTERNAL
SYSTEM FAULT
DOES THE BURNER
EXTINGUISH WHEN THE DHW
TAP IS CLOSED
REPLACE FAULTY PCB
REPLACE FAULTY
FLOWSWITCH
THE BOILER IS OPERATING
REPLACE THE DHW
THERMISTOR.IS THE
WATER TEMPERATURE
NOW STABLE
NO
NO
NO
NO
YES
YES
YES
YES
CHECK THE 3 WAY VALVE
THERMOSTATIC ELEMENT.
IS THE SPINDLE FULLY
EXTENDED
NO
NO
YES
NO
NO
YES
IS THERE CONTINUITY
ACROSS THE DHW
FLOWSWITCH WHEN NO
DHW IS FLOWING
YES
YES