Button
Response
Default Function
Operation
GFCI Test Button
Off
Press and hold until GFCI trips,
no longer than 7 seconds.
GFCI Trip Test
Indicator
Light Off
Red LED illuminates under
GFCI letters when GFCI Test
Button is pushed and goes out
when GFCI is tripped.
Electrical Specifications
15
Receiver
Item
Range/Specs
Remarks
NCV Range
80-300VAC, 60Hz,
1” of the energized
conductor
The receiver tip must be within 2cm
of the energized conductor in order to
sense the presence of AC voltage.
NCV Signal
Indications
The red LED flashes and the buzzer beeps intermittently (beeps
frequency according to the sense voltage, 35V: 2Hz flash/beep;
60V: 4Hz flash, 4Hz beep; 85V: 10Hz flash, 10Hz beep)
Battery
9V
Power Consumption Max 60mA @ 9V
Power off: 2uA
Battery Life
2.5 hrs.
Buzzer Volume
Approximate 60dB @ 10cm
Transmitter
Item
Range/Specs
Remarks
Operating Voltage
100-120V AC
Use for 3 wire North American outlets only
(100-120V AC).
Operating
Frequency
60Hz
GFCI Trigger
Current
6.0mA-9.0mA
GFCI test voltage range AC: 102V
(6mA) - 132V(9mA), only GFCI trip is
triggered(under normal voltage range and
correct wiring, pressing the GFCI button
will trigger GFCI function)
Power Consumption 120V AC Max 1.5W
GFCI Button
Press the GFCI button to start the GFCI test; release the GFCI
button to stop the GFCI test; (Note: Pressing time is less than 6
seconds, it should trigger the switch to trip. If the pressing time
is greater than 6 seconds, and the breaker/outlet does not trip,
the breaker/outlet may be broken or the GFCI function is not
working.) Note: A valid ground conductor must be present for
this test method to work.
Wiring Condition
Indications
100 ~ 120V AC
Overload Protection 240 RMS