FLUE OUTLET
206210-5358b
20 EXAMPlES OF CAlCUlATING FlUE RESISTANCES/lENGTHS - EXAMPlE 2
The total maximum flue resistance for an Evomax 80 is 260 Pa or 12m
80/125. Therefore this installation is acceptable.
Example 2
Vertical Roof Flue for Evomax 80
Resistance (Pa) Resistance (m)
Flue Size
80/125
80/125
Vertical Flue Kit 80/125
135
4.8
2 x 1m extension flue
2 x (21.7)
2 x (1)
2 x 45º elbow
2 x (22)
2 x (1.1)
Total Flue Resistance
222
9
Horizontal Flue for Evomax 40
Resistance (Pa) Resistance (m)
Flue Size
80/125
80/125
Horizontal Wall Flue Kit 80/125
45
7
2 x 1m extension flue
2 x (4.8)
2 x (1)
1 x 90º elbow
14
1.6
Total Flue Resistance
68.6
10.6
19 EXAMPlES OF CAlCUlATING FlUE RESISTANCES/lENGTHS - EXAMPlE 1
206210-5357b
The total maximum flue resistance for an Evomax 40 is 200Pa or 42m
80/125. Therefore this installation is acceptable.
Example 1