Chapter 4
Coax Cable Field Calibration and Testing
4-3
Figure 4-1: IBM COAX Cable Type Screen
For COAX Field Calibration, please follow the instruction below:
1.
Connect the COAX adapters to the Display Handset (DH) and Remote Handset
(RH).
2.
Insert the short COAX calibration cable into both the DH and RH adapters.
3.
From the DH Ready Screen, press F3 or highlight Field Calibration icon and press
ENTER.
4.
Select START by pressing F1 to begin the calibration process. Once the
calibration process completion screen appears, select ESCAPE to return to the
main screen.
5.
When the calibration process is completed, the LANTEK is ready for testing.
Figure 4-2: IBM COAX Field Calibration Screen