DE-COMMISSION
67
Installation and Maintenance
Section 7 - De-Commissioning
7.1 DE-COMMISSIONING
ᘐ
WARNING:
The product contains the fluorinated
refrigerant R-32 which is mildly flammable. The
refrigerant may mix with air to form a flammable
atmosphere increasing the risk of fire and/or explosion.
ᘐ
WARNING: If the Heat Pump is to be permanently
decommissioned this must be carried out by persons
who hold a valid and current F-Gas Directive Cat I or Cat
II certificate.
CAUTION: If the Heat Pump is required to be in-active for
an extended period of time it must not be switched off.
1. Perform safe isolation of all power supplies.
2. Disconnect the appliance from the power supply but
make sure the appliance is still earthed.
3. Drain the heating water from the appliance.
4. Remove service access covers, refer to
Figure 51.
5. Remove the refrigerant from the appliance and
consider the below prior to commencing:
•
Only use tools, electrical power tools and
equipment that are suitable for the intended work
scope.
•
Wear suitable protective personal equipment
(PPE) as necessary.
•
Do not use the appliance compressor to pump the
refrigerant out of the product.
•
Do not attempt to recover the refrigerant whilst the
appliance is switched on.
6. Re-install the right-hand side casing, the front casing,
and the top casing.
7. Clearly label that the appliance so that it is visible
from the outside and explicitly states that it has been
decommissioned and that the refrigerant has been
completely removed.
8. Return the recovered refrigerant in accordance with
F-Gas and local regulations.
9. Dispose of or recycle the appliance and/or its
components in accordance with local laws and
regulations.