background image

14

SECTION 2 - INSTALLATION

2.10 CONDENSATE DRAIN

137

47

156

Condensate

Drain

T

his appliance is fitted with a siphonic 75mm sealed condensate 

trap system that requires filling before operating the appliance for 

the 1st time or after maintenance.
All condensate pipework should conform to the following:

a.  Where a new or replacement boiler is being installed, access to 

an internal ‘gravity discharge’ termination should be one of the 

main factors considered in determining boiler location.

b.  Plastic with push fit or solvent connections.

c.  Internal plastic pipe work a minimum of 19mm ID (typically 

22mm OD)

d.  External plastic pipe must be a minimum of 30mm ID (typically 

32 OD) before it passes through the sleeved wall.

e.  All horizontal pipe runs, must fall a minimum of 45mm per metre 

away from the Boiler.

f.  External & unheated pipe work should be kept to a minimum 

and insulated with Class “O” waterproof pipe insulation.

g.  All installations must be carried out in accordance to the 

relevant connection methods as shown in the “Condensate 

installation diagrams” & BS6798:2009

h.  Pipe work must be installed so that it does not allow spillage 

into the dwelling in the event of a blockage (through freezing)

i.  All internal burrs should be removed from the pipe work and any 

fittings.

NB.  Clip runs to prevent pipework disconnecting due to 

vibration etc.

In order to minimise the risk of freezing during prolonged very cold 

spells, one of the following methods of terminating condensate 

drainage pipe should be adopted.

Internal Drain Connections

Wherever possible, the condensate drainage pipe should be routed 

to drain by gravity to a suitable internal foul water discharge point 

such as an internal soil and vent stack or kitchen or bathroom 

waste pipe etc.  See Figs 1 and 2.

Condensate Pump

Where gravity discharge to an internal termination is not physically 

possible or where very long internal pipe runs would be required 

to reach a suitable discharge point, a condensate pump of a 

specification recommended by the boiler or pump manufacturer 

should be used terminating into a suitable internal foul water 

discharge point such as an internal soil and vent stack or internal 

kitchen or bathroom waste pipe etc. (fig 3).

External Drain Connections

The use of an externally run condensate drainage pipe should 

only be considered after exhausting all internal termination options 

as described previously.  An external system must terminate at a 

suitable foul water discharge point or purpose designed soak away.  

If an external system is chosen then the following measures must 

be adopted:
The external pipe run should be kept to a minimum using the most 

direct and “most vertical” route possible to the discharge point, with 

no horizontal sections in which condensate might collect.
-  For connections to an external soil/vent stack see Fig 4.  

Insulation measures as described should be used.

-  When a rainwater downpipe is used, an air break must be 

installed between the condensate drainage pipe and the 

downpipe to avoid reverse flow of rainwater into the boiler 

should the downpipe become flooded or frozen, see Fig 5.

-  Where the condensate drain pipe terminates in a purpose 

designed soakaway (see BS 6798) any above ground 

condensate drain pipe sections should be run and insulated as 

described above. See Fig 6.

-  Where the condensate drain pipe terminates over an open 

foul drain or gully, the pipe should terminate below the grating 

level, but above water level, to minimise “wind chill” at the open 

end.  The use of a drain cover (as used to prevent blockage by 

leaves) may offer further prevention from wind chill.

Unheated Internal Areas

Internal condensate drain pipes run in unheated areas should be 

treated as external pipe.
Ensure the customer is aware of the effects created by a frozen 

condensate and is shown where this information can be found in 

the user manual.

Boiler

with 75mm 

sealed 

condensate 

trap

Min Ø 19mm 

Internal pipe

Minimum 

connection 

height up to 3 

storeys

Soil & vent stack

≥ 450

Sink/basin/

bath or

shower

Boiler

with 75mm 

sealed 

condensate 

trap

Min Ø 19mm 

Internal pipe

Internal soil & vent stack

≥ 100

Figure 1

 - Connection of Condensate Drainage Pipe to 

Internal Soil & Vent Stack

Figure 2

 - Connection of a Condensate Drainage Pipe 

Downstream of a Sink, Basin, Bath or Shower Water Trap to 

Internal Soil Vent Stack

continued . . . . . 

Summary of Contents for III Series

Page 1: ...co uk To Domestic Hot Water GB24 Propane Minimum 4 9 kW 16 600 Btu h GB30 Propane Minimum 6 1 kW 20 700 Btu h GB24 Propane Maximum 24 2 kW 82 570 Btu h GB30 Propane Maximum 30 3 kW 103 384 Btu h To C...

Page 2: ...2 Combination Boiler Destination Country GB UK IE Ireland Ideal GB24 GB30 Series III...

Page 3: ...rk Generator Replacement 23 3 14 Gas Control Valve Replacement 24 3 15 Divterter Valve Actuator Replacement 24 3 16 Condensate Trap Siphon Replacement 25 3 17 Main PCB Replacement 26 3 18 Replacing Th...

Page 4: ...rformance Data Domestic Hot Water Required for maximum flow rate Boiler operates down to 2 l min DHW delivery Ideal GB Series III 24 30 Gas Supply I3P G31 37mbar Gas Supply Connection 15mm copper comp...

Page 5: ...draw off of 24 9 9 l min at 35 o C temperature rise 30 12 4 l min at 35 o C temperature rise The DHW draw off rate specified above is the nominal that the boiler flow regulator will give Due to system...

Page 6: ...Gas Installer In the approved country the boiler is installed this must be in accordance with their current rules in force Detailed recommendations are contained in the following British Standard Code...

Page 7: ...e length of flue required the flue must be fitted from the outside Installation from inside ONLY b If a core boring tool or hole cutter is to be used inside the dwelling the space in which the boiler...

Page 8: ...CTOR ASSEMBLY 214 VENTURI 215 FAN 217 BURNER 218 GASKET BURNER 219 SUMP CLEAN OUT COVER 223 FLUE MANIFOLD 224 FLUE MANIFOLD TOP 227 CLAMP RETAINING FLUE TURRET 228 HOSE CONDENSATE INTERNAL 229 SIPHON...

Page 9: ...e air duct MUST be sealed with sealant to create an adequate seal WALL Aluminium Flue Collar RSF 060 Fill with sealant 17mm min Internal Sealing Flubber Fill with sealant It is IMPORTANT that all atta...

Page 10: ...outer edge to aid assembly Centre of turret to edge of turret 100mm Turret has a flue insertion of 30mm The white outer flue tube must protrude the wall by 17mm From centreline of turret to wall Rear...

Page 11: ...turret on until it has travelled 30mm on to the flue pipe and is fully engaged Make sure the flue has not rotated or moved forward during fitting and the flue seam is upper most 3 Push the turret into...

Page 12: ...e boiler and its flue system Note The resistance of the deflector is equivalent to 1 metre of flue length Ensure this is used when calculating the maximum allowable flue length 2 Choose the direction...

Page 13: ...alcony 500 mm Below velux windows 2000mm Above or side of velux windows 600mm 2 9 ASSEMBLING THE ROOF FLUE KIT 1 Position the roof plate supplied separately over the hole cut in the roof and insert fl...

Page 14: ...nating into a suitable internal foul water discharge point such as an internal soil and vent stack or internal kitchen or bathroom waste pipe etc fig 3 External Drain Connections The use of an externa...

Page 15: ...ater Weather proof insulation Max 3m external pipework Limestone chippings 500 300 25 2 rows of three 12mm holes 25mm centres 50mm from the bottom of the tube facing away from the house Minimum connec...

Page 16: ...E DHW LIVE X3 PUMP GND X9 X8 OWC OWC OPENTHERM OPENTHERM CHIP COM BUS TX CHIP COM BUS 24V CHIP COM BUS GND CHIP COM BUS 5V CHIP COM BUS RX MAINS LIVE MAINS NEUTRAL AUXILIARY LIVE IONISATION FLOW DHW D...

Page 17: ...leaning procedures are covered more fully in Sections 3 3 3 7 and MUST be carried out in sequence IMPORTANT 6 After completing the servicing or exchange of components always ensure all gas valve conne...

Page 18: ...onto the top retaining clips 5 Retain the upper panel with the two fixing screws previously removed ensuring a good seal is made 6 Swing the lower front panel up and retain with the two screws 7 Close...

Page 19: ...er head is a ceramic plaque construction Care must be taken to ensure that the burner is not placed down upon its face as this may cause damage to the ceramic 6 Brush off any deposits that may be on t...

Page 20: ...nition gap is correct Refer to Sections 3 12 3 13 1 Ignition Electrode Earth Wire Reassemble the boiler in the following order 1 Ensure that the condensate trap siphon is full of water 2 Refit the bur...

Page 21: ...to Section 3 19 THE BOILER MUST NOT BE OPERATED WITHOUT THE FRONT PANEL FITTED 3 9 FAN REPLACEMENT 1 Refer to Section 3 8 2 Disconnect the electrical leads from the fan 3 Remove the clip from the gas...

Page 22: ...any damaged or deteriorating sealing gasket 8 Reassemble in reverse order 9 Check the operation of the boiler 1 Refer to Section 3 8 2 Disconnect the electrical leads from the fan 3 Remove the clip fr...

Page 23: ...the electrode 7 Fit the new ignition electrode using the new gasket supplied Check dimensions as shown 8 Reassemble in reverse order 9 Check the operation of the boiler Ignition Electrode 3mm Straigh...

Page 24: ...ATOR REPLACEMENT Refer to Section 3 8 To remove the motor 1 Remove the condensate trap siphon Refer to Section 3 16 2 Place a flat bladed screwdriver in the actuator slot provided and ease out the act...

Page 25: ...off the rubber pipe at the siphon 3 Turn the siphon clockwise to disengage and lift to remove 4 Reassemble in reverse order 5 When reassembling ensure the trap is full of water 6 Check operation of t...

Page 26: ...uide and secure this to the new PCB 9 Insert the new PCB and secure all electrical connections Ensure control knobs are correctly aligned with PCB 10 Reassemble in reverse order If programming of the...

Page 27: ...ill be experienced during replacement of components 3 After replacing any component on the boiler DHW circuit re fill as appropriate 4 Check operation of the boiler CENTRAL HEATING CIRCUIT 1 Refer to...

Page 28: ...reeze Check operation of the boiler 5 7 4 1 Refer to Section 3 8 2 Drain the heating system Refer to Section 3 19 3 Remove the boiler front See Section 3 8 lower the control panel and remove the contr...

Page 29: ...7 Remove the pump electrical connection Refer to Section 3 26 no 3 8 Remove DHW Turbine electrical connection Refer to Section 3 20 no 3 9 Remove the DHW plate heat exchanger note orientation Refer to...

Page 30: ...g a suitable tool pull out the metal retaining clip 5 Carefully withdraw the pressure switch 6 Fit the new pressure switch and re assemble in reverse order 7 Refill the boiler and add the correct volu...

Page 31: ...anner should be used 5 Fit the new thermistor using the sealing washer provided 6 Reassemble in the reverse order 7 Refill the boiler and add the correct volume of anti freeze 8 Check the operation of...

Page 32: ...llows clearance of the pipe from heat exchanger plugs Lift pipe and remove 13 Remove the two heat exchanger fixing screws 14 To remove the Heat exchanger slide out of location bracket 15 Remove the co...

Page 33: ...pressure to 0 75 bar 5 Re assemble in reverse order re fill the boiler and add the correct volume of anti freeze 6 Check operation of the boiler REPLACEMENT 7 Refer to Section 3 8 8 Drain the boiler C...

Page 34: ...r hot water but the appliance has reached the desired temperature set on the boiler The boiler is operating in central heating mode The boiler is operating in domestic hot water mode The boiler is ope...

Page 35: ...er letter refer to page 34 L Boiler is in lockout for a specific error Display will show L with a number or letter to show which error is detected F Boiler has a fault for a specific error Display wil...

Page 36: ...e house are working to confirm a supply is present in the property 3 If other appliances do not work or there are no other appliances check the gas supply is on at the meter and or pre payment meter h...

Page 37: ...FAULT GO TO SECTION 4 13 RETURN THERMISTOR FAULT GO TO SECTION 4 14 OUTSIDE SENSOR FAULT LOW MAINS VOLTAGE CONTACT ELECTRICITY PROVIDER NEGATIVE DIFFERENTIAL FLOW OR RETURN THERMISTOR FAULT PCB UNCONF...

Page 38: ...Check wiring connection from gas valve to PCB for continuity If the wiring is OK then replace the PCB NO Replace Spark Generator and harness as necessary NO Replace ignition detection electrode and a...

Page 39: ...Are the Boiler and CH System filled with water and radiator valves open check pressure gauge is between 1 to 1 5 bar NO NO YES Fill and vent the system and open all isolation valves YES Are connection...

Page 40: ...lectrode and associated harness for continuity visual condition and position Refer to Section 3 12 Are these functioning correctly YES Check siphon and condensate drain pipe work for blockage and rect...

Page 41: ...NO Securely connect the wiring to the PCB Is the wiring securely connected to the Flow Thermistor located in the top of the Heat Exchanger YES NO Securely connect the wiring to the Flow Thermistor NO...

Page 42: ...Disconnect the wires to the outside sensor Check the resistance using a suitable multimeter connected across the Outside Sensor s terminal pins At 0 o C expect 31 000 35 000 Ohms At 15 o C expect 15...

Page 43: ...rise and check filter fitted in turbine is not blocked with debris NO Reconnect wiring or replace wiring harness if no continuity NO Re engage diverter head NO Replace PCB Is hot and cold pipework cr...

Page 44: ...spare parts product training please phone us on 01482 325456 or contact us at the address below MORCO PRODUCTS LTD Morco House Riverview Road Beverley East Yorkshire HU17 0LD TEL 01482 325456 FAX 014...

Reviews: