Weather Compensation Kit - 

Installation

INTRODUCTION

T

his kit provides the facility to apply outside air temperature control to the boiler water flow temperature which provides 

energy savings.  The outside sensor provided measures outside air temperature and sends a signal to the boiler, which 

adjusts the maximum boiler flow temperature in response.  If outside air temperature is greater than the system design 

temperature, the boiler flow temperature is reduced providing running cost savings.  The boiler will operate in the 

condensing mode more frequently increasing savings.  
Once the sensor is fitted it is automatically detected.  
The sensor operation may be configured by adjustment of the boiler operating parameters, if necessary.

1  KIT CONTENTS

C

A.  Outside Air Sensor

B.  SAP Registration Label

C.  Connector

     (Required only for boilers

      marked with *.  See above)

B

A

Model Name:
Model Qualifier:

Signed:

Date:

UIN 212050 A01

OS2
ErP Class II

IDEAL BOILERS LTD

I certify that this boiler is connected to a weather 

compensation  temperature  sensor  which  is 

compatible with the boiler and provides weather 

compensation  control  that  has  been 

permanently  enabled.   The  boiler  has  been 

commissioned in accordance with manufacturer 

instructions,  which  have  been  supplied  to  the 

householder.  The central heating temperature 

control  knob  should  normally  be  set  in  the 

mid-position.

Terminal block

(2 way)

wire connection

Cable Entry

Fixing screw & wall plug

supplied inside cover

NOTE.

To be mounted onto wall

in orientation shown

Clip on

cover

Ideal OS2 (Outside Sensor 2)

Class 

II

 used in isolation, Class 

VI

 used with Ideal PRT4

Contribution to Seasonal Space Heating Energy - 2% (Class 

II

), 4% (Class 

VI

)

* Refer to Frame 1, item C.

This kit is suitable only for the domestic gas boilers listed below:

COMBI BOILERS

*Logic Combi C
*Logic Combi C IE
Logic Combi ESP1
Logic Code Combi ESP1
Logic+ Combi C
*Independent Combi
*Inde Combi
*i-mini C
Vogue Combi C GEN2
Vogue Combi C IE GEN2
Logic Max Combi C
Vogue Max Combi

HEAT BOILERS

Logic Heat H
Logic Heat H IE
Logic+ Heat H
Logic Max Heat H

SYSTEM BOILERS

Logic System S
Logic System S IE
Logic+ System S
Vogue System S GEN2
Vogue System S IE GEN2
Logic Max System S
Vogue Max System

Summary of Contents for Logic Combi C

Page 1: ... we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers For the very latest copy of literature for specification and maintenance practices visit our website www idealboilers com where you can download the relevant information in PDF format September 2018 UIN 216120 A09 WEATHER COMPENSATION KIT ...

Page 2: ...ather compensation temperature sensor which is compatible with the boiler and provides weather compensation control that has been permanently enabled The boiler has been commissioned in accordance with manufacturer instructions which have been supplied to the householder The central heating temperature control knob should normally be set in the mid position Terminal block 2 way wire connection Cab...

Page 3: ...s connection is protected extra low voltage It is not necessary for the person carrying out the wiring to be approved to Part P of the Building Regulations Avoid running this cable alongside mains voltage cables WIRING THE WEATHER COMPENSATION KIT TO THE BOILER 1 Isolate the electricity supply to the boiler 2 Remove the boiler front panel refer to boiler installation instructions 3 Hinge down the ...

Page 4: ...Z E t K KE t KE Z z W E s s d D Z Ž Ő ǁ Ő LJ ď N L BLR ON C S ON HW OFF HW ON R S ON CH ON E L FUSED SPUR SYSTEM BOILER WITH S PLAN OUTSIDE SENSOR L N HW OFF CH ON HW ON R S C S S PLAN VALVE HW TIMER S PLAN VALVE CH g y b br o br o N E L IN L IN L N E sL2 sL1 MAINS IN BOILER g y b g g SYSTEM BOILER WITH S PLAN SYSTEM OUTSIDE SENSOR KIT SYSTEM BOILER WITH Y PLAN SYSTEM OUTSIDE SENSOR KIT ...

Page 5: ...E E h WhZ d K Z t d z W E Θ Khd E KZ E t K KE t KE Z z W E s s d D Z WhDW ď Ž Ő ǁ Ő LJ Ž Ő LJ KE t K t KE Z KE KE E Z KE h WhZ d K Z t d W E Θ Khd E KZ E t K KE t KE Z W E s s t d D Z E E E Ɛ Ϯ Ɛ ϭ D E E K Z W E s s WhDW Ő ď ďƌ Ž ďƌ E Ő LJ ď Ő HEAT BOILER WITH S PLAN SYSTEM OUTSIDE SENSOR KIT HEAT BOILER WITH Y PLAN SYSTEM OUTSIDE SENSOR KIT ...

Page 6: ...LY N L BLR HW C S ON HW OFF HW ON R S ON CH ON E L FUSED SPUR SYSTEM BOILER WITH S PLAN OUTSIDE SENSOR L N HW OFF CH ON HW ON R S C S S PLAN VALVE HW TIMER S PLAN VALVE CH g y b br o br o N E L IN L IN L N E sL2 sL1 MAINS IN BOILER g y b g g BLR CH SYSTEM BOILER WITH S PLAN SYSTEM OUTSIDE SENSOR KIT ...

Page 7: ...splay the Room Temperature Setpoint will be 22ºC and the curve 22 will be followed indicated by 11th curve in from the left hand side So as the outside temperature varies the Flow Setpoint to the CH circuit will increase and decrease proportionally 2 If the CH Potentiometer Knob is rotated fully clockwise the Boiler Display will read 30ºC and the Room Temperature Setpoint will be 30ºC hence the cu...

Page 8: ...l Training The Ideal Technical Training Centre offers a series of first class training courses for domestic commercial and industrial heating installers engineers and system specifiers For details of courses please ring 01482 498432 Ideal Boilers Ltd PO Box 103 National Avenue Kingston Upon Hull HU5 4JN Tel 01482 492251 Fax 01482 448858 Registration No London 322 137 Ideal Technical Helpline 01482...

Reviews: