Installation & Servicing
SERVICING
3
Seals
nm8201
67 BOILER SEALING PANEL SEAL REPLACEMENT
1.
Refer Frame 52.
2.
Remove the front panel. Refer to Frame 45.
3.
Remove the boiler sealing panel. Refer to Frame 46.
4.
Remove the old seal from the casing and thoroughly
clean the casing surfaces.
5.
Fit the new adhesive seals - note that they are
supplied to the correct length for the relevant sides.
6.
Reassemble in reverse order.
Note.
Ensure that the boiler sealing panel is correctly
seated, compressing the seal to make an airtight
joint.
7.
Check operation of boiler.
Refer to
Frame 52.
1.
Refer to Frame 52.
2.
Remove the boiler front panel. Refer to Frame 45.
3.
Undo the plastic union nut on the condensate 'S' trap
outlet and disconnect the flexible hose.
4
. Remove the screw retaining the ‘S’ trap bracket and
remove the bracket.
68 CONDENSATE ‘S’ TRAP REPLACEMENT
5.
Loosen the top nut on the ‘S’ trap then pull the trap
down and forward to remove.
6.
Reassemble in reverse order.
7.
Check operation of the boiler. Refer to Frame 52.
SER
VICING
3
4
5
202414-6.pmd
19/02/2008, 13:08
43