17
classic m -
Installation & Servicing
INSTALLATION
FLUE OUTLET
1.
A
maximum
of 3 extension ducts (one suitably
cut) plus the standard flue duct may be used
together.
2.
Flue extensions of greater length than 1m (39")
should be supported with the bracket provided,
suitably adjusted. Refer to Frame 24.
21 FLUE EXTENSION DUCTS - continued
1.
Remove the cardboard support aid from the flue and
place safely to one side.
2.
Fit the inner flue extension duct onto the inner flue duct.
3.
Fit the outer flue extension duct onto the outer air duct.
4.
Using the clamp provided clamp the flue lengths together.
5.
Repeat steps 1-4 if a second flue extension is required.
6.
Measure and mark the flue length required onto the flue,
measuring from the groove near the terminal.
7.
To ensure a square cut, mark the flue all the way round.
8.
Cut to length using the cardboard support aid.
9.
Remove the cardboard off-cut and deburr the metal
edges.
22 FITTING THE KIT
20 FLUE EXTENSION DUCTS - For flue lengths greater than 480mm
Pack D Flue extension duct kit contents.
Note.
Side flue shown
Use a maximum of 3m extended flue ONLY
General arrangement
Flue duct support
Flue support cutting aid
(shown folded up)
Wall plugs - 4 off
Extension duct & clamp
1.0m (39") long
No. 10 x2" wood screw - 4 off
Ecl 1244
Ecl 1591
Boiler
Standard flue
Terminal grille
Flue length
Extension flue
GROOVE
2
3
9
Ecl 1532