Classic Combi FF 280 -
Installation
21
INSTALLATION
SIDE FLUE OUT
LET
General arrangement
Note.
Side flue shown.
1.
A
maximum
of 2 extension ducts (plus the standard flue
duct) may be used together.
2.
Flue extensions of greater length than 1m (39") should be
supported with the bracket provided. If the stand-off
brackets have been used it is necessary, in order to keep
the flue aligned, to use the spacer bracket with the support
bracket.
Flue length
Accessories
Product No.
Up to 600
B Pack 1 off
see Frame 3
600 to 1800
B Pack 1 off + D Pack, 1 off
see Frame 3
1800 to 3000
B Pack 1 off + D Pack, 2 off
see Frame 3
Use a maximum of two extension ducts only
36 FLUE EXTENSION DUCTS - continued
35 FLUE EXTENSION DUCTS - For flue lengths greater than 600mm
34 TERMINAL WALL PLATE
This plate allows neat concealment and full compression of the
rubber seal. Its use is not essential if the flue hole and flue ducts
have been accurately cut and the outside wall face is flat.
1.
Position the terminal wall plate over the terminal.
2.
Drill 4 fixing holes with an 7mm (
9/32
") masonry drill.
3.
Insert the 4 plastic plugs provided.
4.
Secure the plate with 4 of the No.10 x 2" screws provided.
Note.
If the terminal is less than 2m (6' 6") above ground level, an
approved terminal guard should be fitted. Refer to the contents
list on Page 2.
PACK D Flue Extension Duct Kit contents
Flue length
Extension duct
Flue connector
Standard flue
Terminal grille
Boiler
Extension
tube
Wall plug
No. 8 x 1/4" self
tapping screws - 14 off
No. 10 x 3" wood screw -1off
Support bracket
Extension duct
1.2m (42") long
Flue connectors - 2 off