3.1 Installation and connection

Read  these  instructions  before  installing  the  char-
ging station carefully. Alfen ICU B.V. are not liable 
for  any  consequential  damages  that  occur  due  to 
the use of this manual.

The installation must be performed by qualified 
personnel that have read this manual and opera

-

te in accordance with the guidelines IEC 60364.  
Otherwise it may result in injury or dangerous si

-

tuations when dealing with electricity.

NOTICE

Work may not be performed when it is raining or 
the air humidity is higher than 95%.

NOTICE

A charging station should always be installed on 

a dedicated circuit.

NOTICE

Danger to life through improper installation! 

Non-observance of the following installation and 
environmental requirements can lead to dange

-

rous situations when dealing with electricity.

!

DANGER!

The electrical system must be dead (disconnec

-

ted from the power supply) during all installation 
and maintenance work.

!

DANGER!

3.2  Requirements  for  assembly  and  
installation

Cables should be laid based on maximum char

-

ging  rate  of  the  charging  station  under  conti-

nuous  load  (no  diversity).  The  cable  diameters 
in  this  manual  are  indicative.  The  technician  is 

responsible for determining the correct cable dia-

meter and compliance with applicable standards.

NOTICE

Make  sure  that  the  following  requirements  for  the 
installation of the ICU Eve are fulfilled:

• 

The  cable  route  from  the  main  distribution  to 

the ICU Eve must be secured with a miniature 
circuit breaker (MCB) with characteristic B or a 
screw or blade fuse gG against overvoltage and 

short circuit

• 

The cable route must be secured against acci-

dental contact 30 mA by a type A or B-residual-

current circuit breaker 

• 

The  cable  route  and  the  charging  station  are 

part of a TN-S system; the device is grounded 
via the main distributor

3. Mounting and connecting

Type

Protection Option 1

Protection Option 2

Min. core 
cross section

1 x type 2 charging 

socket, 3-phase, 16 A

3 x 20 A gG fuses + 20 A - 30 mA 

residual-current circuit breaker

20 B - 30 mA 4p 

 

residual-current fuse

5 x 4 mm

2

1 x type 2 charging 

socket, 3-phase, 32 A

3 x 35 A gG3 fuses + 40 A - 30 mA 

residual-current circuit breaker

40 B - 30 mA 4p 

 

residual-current fuse

5 x 6 mm

2

2 x type 2 charging 

socket, 1-phase, 16 A

1 x 35 A gG fuses + 40 A - 30 mA 

residual-current circuit breaker

40 B - 30 mA 2p 

 

residual-current fuse

3 x 6 mm

2

2 x type 2 charging 

socket, 3-phase, 16 A

3 x 35 A gG fuses + 40 A - 30 mA 

residual-current circuit breaker

40 B - 30 mA 4p 

 

residual-current fuse 

5 x 6 mm

2

2 x type 2 charging 

socket, 3-phase, 32 A

3 x 80 A gG fuses + 80 A - 30 mA 

residual-current circuit breaker 

3 x 80 B system fuse + 
80 A - 30 mA residual-

current circuit breaker

5 x 16 mm

2

Mounting and connecting

The table below shows the safety options and the necessary cable diameters:

Summary of Contents for EVE

Page 1: ...ICU Eve TM MANUAL HANDBOEK ANLEITUNG MANUEL MANUALE ...

Page 2: ...t Verpackung Contenu de l emballage Contenuto della confezione ICU Eve Pole Paal Säule Pôle Polo 1 x 1 x 1 x 1 x 1 x 1 x 1 x 1 x 1 x 4 x 4 x Anti theft M4 x 12 M10 M10 Plug Charge RFID RFID Display Types Varianten Varianten Variantes Varianti ...

Page 3: ...Outside Buiten Außen Extérieur Esterno 1 2 4 5 H x W x D 590 x 338 x 230 mm INTERFACE ANPASSEN 9 9 6 7 8 3 ...

Page 4: ...Inside Binnenzijde Innen Intérieur Interno 10 11 13 14 12 ...

Page 5: ...Installation Installatie Installation Installation Installazione 1364 650 ...

Page 6: ...or or Operating Operating Betrieb Opération Operazione Charging station with RFID card Plug Charge Authorisation without charging card Start 1 2 3 4 Start 1 2 3 Stop 1 2 3 Stop 1 2 3 4 3 sec 3 sec ...

Page 7: ...tbus 1042 1300 BA Almere Tel 31 36 54 93 400 E mail info icu charging stations com Website www icu charging stations com Contact Contact Kontakt Contact Contatto Status LED Status LED Status LED LED d état LED di stato 15 16 17 18 19 20 21 22 Flicker Flicker Flicker ...

Page 8: ...Alfen ICU B V Splijtbakweg 15 Almere NL Tel 31 36 549 34 00 E mail info icu charging stations com www icu charging stations com Subject to modifications and amendments ...

Page 9: ... 9 4 2 Putting into operation 9 5 Connectivity 10 5 1 Backend Services 10 5 2 UTP Ethernet connection 10 5 3 Registering your ICU EZ account 10 Declaration of Conformity Name of manufacturer Alfen ICU B V Splijtbakweg 15 1333 HC Almere The Netherlands Declares the conformity of the product Charging stations of Type ICU Eve Following the Euopean Directives Low Voltage Directive 2014 35 EU EMC direc...

Page 10: ...es are close If the product is in the water At ambient temperatures of less than 30 C or over 40 C When the product or individual components are damaged For children or persons who can not assess the risk in handling the product In the following cases Alfen ICU B V accepts no liability for damages The warranty on products and accessories expires in the following cases Failure to follow these Insta...

Page 11: ... for cable to be connected 17 The charging station and vehicle are communicating Electric vehicle is full or charging is on hold 18 Vehicle is charging 19 External error The cable has been left too long in the charging station without starting a charging process 20 The charging station has an internal error 21 The card reader is active 22 The used card is not authorized Product Identification Labe...

Page 12: ...A 400 V Output vehicle connection Connection system 1 or 2 x type 2 connector type 2 S France only in accordance with IEC62196 2 Output Voltage 230 V or 400 V Max charging current 16 A 1 phase or 16 A 3 phase or 32 A 3 phase Max output 3 7 kW or 7 4 kW or 11 kW or 22 kW Shut down Standby all contacts Dynamic load balancing yes optional Protection integrated compo nents RCCB integrated RCCB Type B ...

Page 13: ...ICU Connect optional or other backend on request Communication with Smart Meter P1 Port Operating conditions Operating temperature 30 C to 40 C Relative humidity 5 to 95 Class of protection I Degree of protection housing IP54 IK Protection IK10 Stand By consumption C 20 W Housing Type Wall mounted housing Fixing type Plug and screw mounting or screwed to a pole optional Material cover Fiberglass r...

Page 14: ...ure that the following requirements for the installation of the ICU Eve are fulfilled The cable route from the main distribution to the ICU Eve must be secured with a miniature circuit breaker MCB with characteristic B or a screw or blade fuse gG against overvoltage and short circuit The cable route must be secured against acci dental contact 30 mA by a type A or B residual current circuit breaker...

Page 15: ...n when it is connected to the vehicle It should not be possible to drive over the cable 3 3 Mechanical installation The following tools and materials to install the ICU Eve Spirit level Impact Drill Screwdriver for an M5 cross recess hole Screwdriver for a terminal block Pencil and provided drilling template Torx M5 T25 Wire Stripper Allen key 4 x M5 x 30mm screws 4 x M5 x 30mm plugs 4 x M5 rings ...

Page 16: ...ing unit and is secured with two screws at the top and bottom 1 Place the device on its back 2 Loosen the screws on the bottom with an Allen key 3 Loosen with a Torx M5 T25 the two screws on the side of the rear housing 4 Keep the screws in a safe place they will be required later 5 Lift the front cover from the bottom upwards 6 Loosen the wiring of the LED and optional on the display 13 on the le...

Page 17: ...ating Follow the below safety instructions before putting your charger into operation 1 Make sure that the charging station is securely connected to the house supply line as specified in this manual 2 Make sure that the supply line in the house dis tribution is separately protected by an appropri ate circuit breaker B characteristic 3 Make sure that the built in charger or external upstream RCD is...

Page 18: ...station 12 on the left of the cover 4 Turn on the power of the charging station by putting the main switch to the 1 position 5 In order for your charging station to communi cate with ICU EZ through a wired UTP ethernet connection your network setting should be ad justed if these are additionally secured Below you will find the necessary information to allow access through your network IP address I...

Page 19: ...11 ENGLISH EN ...

Reviews: