3.1 Installation and connection

Read these instructions before installing the char-

ging station carefully. Alfen ICU B.V. are not liable 

for any consequential damages that occur due to 

the use of this manual.

The installation must be performed by qualified 

personnel that have read this manual and opera-

te in accordance with the guidelines IEC 60364.  

Otherwise it may result in injury or dangerous si-

tuations when dealing with electricity.

NOTICE

Work may not be performed when it is raining or 

the air humidity is higher than 95%.

NOTICE

A charging station should always be installed on 

a dedicated circuit.

NOTICE

Danger to life through improper installation! 

Non-observance of the following installation and 

environmental requirements can lead to dange-

rous situations when dealing with electricity.

!

DANGER!

The electrical system must be dead (disconnec-

ted from the power supply) during all installation 

and maintenance work.

!

DANGER!

 

3.2 Requirements for assembly and 

 

installation

Always  carry  out  the  wiring  at  the  maximum 

charging current of the charging point with a 

continuous  load.  The  cable  thicknesses  in  this 

manual are indicative. The installer is always re-

sponsible for determining the correct cable thick-

ness on site and the application of the applicable 

standards. 

NOTICE

Make  sure  that  the  following  requirements  for  the 

installation of the ICU Eve Mini are fulfilled:
•  The cable route of the main distributor to the 

ICU Eve Mini must be protected against power 

surges and short-circuits by using a B characte-

ristic circuit breaker or a screw gG tag fuse

•  The cable route must be protected against acci-

dental touching by a type A or B 30 mA residual 

current

•  The cable route and charging point are a part 

of a TN-S system and the earthing is provided 

from the main distributor

•  The cable route must be laid in accordance with 

the applicable standards

•  The cable tray is made of copper cable with 

The cable route consists of copper cable where 

90°C is at least the highest allowed conductive 

temperature

3. Mounting and connecting

Type

Protection Option 1

Protection Option 2

Min. core 

cross section

1 Socket Eve - Type 2, 

1-phase, 16 A

1 x 20 A gG-fuses + 20 A - 30 mA 

RCD

20 B - 30 mA 1p + N  

residual current fuse

3 x 4 mm²

1 Socket Eve - Type 2, 

3-phase, 16 A

3 x 20 A gG-fuses + 20 A - 30 mA 

RCD

20 B - 30 mA 4p 

residual current fuse

5 x 4 mm²

1 Socket Eve - Type 2, 

3-phase, 32 A

3 x 35 A gG-fuses + 40 A - 30 mA 

RCD

40 B - 30 mA 4p 

residual current fuse

5 x 6 mm²

Mounting and connecting

The table below shows the safety options and the advised cable diameters:

Summary of Contents for Eve Mini

Page 1: ...lay 10 4 3 Putting into operation without display 10 5 Connectivity 11 5 1 Back Office Services 11 5 2 UTP Ethernet connection 11 5 3 Registering your ICU EZ account 11 Declaration of Conformity Name...

Page 2: ...bited When explosive or highly flammable substan ces are close If the product is in water At ambient temperatures of less than 25 C or over 40 C When the product or individual components are damaged F...

Page 3: ...block for power cable 13 UTP Ethernet and P1 port connection Product Identification Label The identification label 5 specifies for example the model production date and serial number It can be found...

Page 4: ...entification with RFID is done and now waiting for cable to be connected 15 The charging station and vehicle are communicating 16 Vehicle is charging Smart charging in progress 17 The charging is comp...

Page 5: ...lamps max 10 mm main switch Grounding TN S System PE wire Output vehicle connection Connection system 1 x type 1 or type 2 connector in accordance with IEC62196 2 Output Voltage 230 V or 400 V Max cha...

Page 6: ...l or other backend on request Communication with Smart Meter UTP cable with RJ11 plug Operating conditions Operating temperature 25 C to 40 C Relative humidity 5 to 95 Class of protection I Degree of...

Page 7: ...ponsible for determining the correct cable thick ness on site and the application of the applicable standards NOTICE Make sure that the following requirements for the installation of the ICU Eve Mini...

Page 8: ...ot be possible to drive over the char ging cable 3 3 Mechanical installation The following tools and materials to install the ICU Eve Mini Spirit level Impact Drill Screwdriver for a terminal block Pe...

Page 9: ...wall plugs into the four holes 2 Attach the ICU Eve Mini on the wall with four M8 x 12 mm screws 3 4 Electrical Installation Read and follow all safety instructions in this manual CAUTION The electri...

Page 10: ...ected by an appropri ate circuit breaker B characteristic 3 Make sure that the built in charger or external upstream RCD is switched on 4 Make sure that the charging station has been installed in acco...

Page 11: ...tation via UTP Ethernet cable to the internet 5 2 UTP Ethernet connection Which cable is required A UTP cable of minimally CAT5 is needed to con nect the charging station to the Internet This cable is...

Reviews: