ENGLISH
EN
3.1 Installation and connection
Read these instructions before installing the char-
ging station carefully. Alfen ICU B.V. are not liable
for any consequential damages that occur due to
the use of this manual.
The installation must be performed by qualified
personnel that have read this manual and opera-
te in accordance with the guidelines IEC 60364.
Otherwise it may result in injury or dangerous si-
tuations when dealing with electricity.
NOTICE
Work may not be performed when it is raining or
the air humidity is higher than 95%.
NOTICE
A charging station should always be installed on
a dedicated circuit.
NOTICE
Danger to life through improper installation!
Non-observance of the following installation and
environmental requirements can lead to dange-
rous situations when dealing with electricity.
!
DANGER!
The electrical system must be dead (disconnec-
ted from the power supply) during all installation
and maintenance work.
!
DANGER!
3.2 Requirements for assembly and
installation
Always carry out the wiring at the maximum
charging current of the charging point with a
continuous load. The cable thicknesses in this
manual are indicative. The installer is always re-
sponsible for determining the correct cable thick-
ness on site and the application of the applicable
standards.
NOTICE
Make sure that the following requirements for the
installation of the ICU Eve Mini are fulfilled:
• The cable route of the main distributor to the
ICU Eve Mini must be protected against power
surges and short-circuits by using a B characte-
ristic circuit breaker or a screw gG tag fuse
• The cable route must be protected against acci-
dental touching by a type A or B 30 mA residual
current
• The cable route and charging point are a part
of a TN-S system and the earthing is provided
from the main distributor
• The cable route must be laid in accordance with
the applicable standards
• The cable tray is made of copper cable with
The cable route consists of copper cable where
90°C is at least the highest allowed conductive
temperature
3. Mounting and connecting
Type
Protection Option 1
Protection Option 2
Min. core
cross section
1 Socket Eve - Type 2,
1-phase, 16 A
1 x 20 A gG-fuses + 20 A - 30 mA
RCD
20 B - 30 mA 1p + N
residual current fuse
3 x 4 mm²
1 Socket Eve - Type 2,
3-phase, 16 A
3 x 20 A gG-fuses + 20 A - 30 mA
RCD
20 B - 30 mA 4p
residual current fuse
5 x 4 mm²
1 Socket Eve - Type 2,
3-phase, 32 A
3 x 35 A gG-fuses + 40 A - 30 mA
RCD
40 B - 30 mA 4p
residual current fuse
5 x 6 mm²
Mounting and connecting
The table below shows the safety options and the advised cable diameters: