Wiring Diagram
Wiring
AUX WIRING: Min 22AWG Max 16AWG. (Depends on
length and Current consumption). For wire/cable size,
a maximum of 5% voltage drop at the terminals of
the powered device has to be observed.
MODULE NETWORK WIRING: Recommended Belden
9842 or equivalent. (24AWG twisted pair with
characteristic impedance of 120ohm or CAT5e / CAT6
are also supported for Data Transmission when using
ground in the same cable. Do not use extra wires to
power devices.) max 900m (3000ft).
Battery Characteristics
Battery Type to be used: VRLA (valve regulated sealed
lead acid type rechargeable battery)
Recommended Battery: Yuasa model:
NP7-12, 12V,7Ah (www.yuasabatteries.com)
Nominal Voltage: 12V
Nominal Capacity: 7Ah
Battery Maintenance: It is recommended to replace
the battery every 3-5 years.
NC
C
N0
C
TP
V+
V
-
Z1
C
Z2
Z3
C
Z4
Input Expander
2A Power Supply
AC Fail Connection
Ensure common ground between devices
NC
C
NO
C
TP
V+
V
-
Z1
C
Z2
Z3
C
Z4
Battery Fail Connection
Ensure common ground between devices
Input Expander
2A Power Supply
Until connection to any System Controller is established, the outputs operate in
Offline Mode. While in offline mode, the 2 outputs function as status outputs.
AC Fail Status Output:
The output relay contacts
disconnect (Normally Open)
when AC power is removed
and unit remains running on
backup battery power. Upon
restoring AC power, the output
relay will revert back to its
default state
(Normally Closed).
Outputs - Offline Mode
Battery Fail Status Output:
The output relay contacts
connects (Normally Closed)
when either the backup battery
has been disconnected, or
when the Power Supply is
running on backup battery
power without AC power and
the backup battery voltage
drops below 11.75V. Upon
reconnecting a backup battery
with a voltage greater than
12.5V, the output relay will
revert back to its default state
(Normally Open).
The outputs are shown to be connected to a DIN Rail 16 Input Expander
so the statuses can be externally monitored.
The address of the 2A Intelligent Power Supply is
configured via programming and will require reference
to the module serial number. The serial number can be
found on the identification sticker on the side of the
module.
Please refer the System Controller Installation Manual for
address programming details.
LED
Description
Power
Green
Correct module input voltage applied.
Off
Incorrect module input voltage applied.
Status
Module successfully registered with controller.
Module attempting registration with controller
Module communication activity.
Fault
Red
ON and OFF rapidly with a delay of 1.5 second between each display cycle.
Number of Flashes
Error Description
1
Unknown Error Code
2
Firmware Version
3
Address Too High
4
Address in Use
5
Controller Secured
6
Serial Number Fault
7
Locked Device
For further details, please refer to the Error Code Display section in the Installation Manual.
V1 Out /
V2 Out
Green
12VDC output operating OK.
Off
12VDC output failure.
Battery
Off
Backup battery is disconnected/failed its dynamic battery test.
Green
Last backup battery dynamic test successful.
Temp
Red
Core temperature exceeded. Over Temp Shutdown Activated.
Core temperature within 15°C of Over Temp Shutdown.
Off
Core temperature OK.
Over
Current
Red
Output current exceeded. Over Current Shutdown Activated.
Off
Maximum output current not exceeded.
Outputs - Online Mode
Upon successfully completing the initial
registration with any System Controller, the
outputs operate in Online Mode. While in
online mode, the 2 outputs function as PGMs
and can be used to activate bell sirens,
lighting circuits, door locks, relay accessory
products and other automation points.
NC
C
NC
C
TP
1K5 OHM
LED
Output Connection
V2+
V-
V1+
V-
CAUTION: INCORRECT
WIRING MAY RESULT
IN DAMAGE TO THE
UNIT
Devices connected to other Modules
Inductive devices (such as electric locking
devices, solenoids, etc) connected to other
modules require a 1N4007 diode to be fitted as
close to the device as possible.
+
-
1N4007 Diode
12VDC Electric
Locking Device
NA
N+
N-
NB
System Controller
The 2A Intelligent Power Supply
should be supplied by a dedicated
electrical power source rated for a
minimum 10Amp load and have a
dedicated circuit breaker. Do not use
a switch controlled breaker or
switched electrical point to supply
power.
Next
modules
on network
NA
N+
N-
NB
White
Blue
Black
Red
Gel Cell
Backup
Battery
(Min 7Ah)
Tamper
Switch
B
ra
ck
et
Gel Cell
Backup
Battery
(Min 7Ah)
Transformer
secondary 16
to 16.5VAC,
50-60Hz 40VA
and greater
ULC-LA AC
Indicator*
Inline
5A 3AG
fuseholder*
+
2A Power Supply
PRT-PSU-DIN-2A | Protege DIN Rail 2A Intelligent Power Supply | Installation Manual