ICT ICT24012-15BC2 Instruction Manual Download Page 3

 

Innovative Circuit Technology Ltd. 

INTRODUCTION 

The ICT BC2 IntelliCharge series of intelligent battery chargers provide reliable dc 
power to a system while precisely maintaining an external back-up battery using 
an intelligent temperature compensated fast-charge algorithm. The wide-ranging 
power factor corrected input supports operation worldwide, while a built in Low 
Voltage Disconnect (LVD) relay will protect the battery from over discharge after 
prolonged periods of backup operation when AC power has failed. Features 
include: 
 

 

Dedicated independently controlled backup battery port with LVD relay 

 

Intelligent 3-stage fast charge algorithm for battery 

 

Optional remote battery temperature sensor for precise charge voltage 
compensation (from -30C to +40C) 

 

Selectable battery charge settings for AGM, Flooded, or Gel batteries, or 
fixed Float voltage operation 

 

Selectable charge rates to accommodate lower capacity batteries 

 

Wide range Power Factor corrected AC input supports operation world 
wide 

 

Floating Form-C alarm contact output supports remote monitoring of 
unit operation 

 

Model

1

 

Output 
Voltage

2

 

Max Output 
Current 

Continuous 
Output Current 

ICT24012-30BC2 

13.65V 

30.0A 

30.0A 

ICT24012-15BC2 

13.65V 

15.0A

3

 

12.0A 

ICT24024-15BC2 

27.3V 

15.0A 

15.0A 

ICT24024-7BC2 

27.3V 

7.5A

3

 

6.0A 

ICT24048-7BC2 

54.6V 

7.5A 

7.5A 

 
Optional Accessories: 
19 inch rack mounting kit (mount up to 2 chargers):   ICT-RMK5 
Remote Battery Temperature Sensor (10ft):  

ICT-TMP 

INSTALLATION 

Perform a quick physical check of the unit as it is being taken out of the box to 
ensure it has not been damaged during shipping. Check for the included parts 
and accessories shipped with your unit: 

 

3 pin Form-C alarm connector plug (installed on unit) 

                                                 

1

 A suffix letter 

“M” 

at the end of the model number is added to denote versions with 

optional front graphic meter display 

2

 Fixed AGM Float Voltage

 

3

 

Max output current less than 10% duty cycle

 

All manuals and user guides at all-guides.com

Summary of Contents for ICT24012-15BC2

Page 1: ...00 Innovative Circuit Technology Ltd Models ICT24012 30BC2 ICT24012 30BC2M ICT24012 15BC2 ICT24012 15BC2M ICT24024 15BC2 ICT24024 15BC2M ICT24024 7BC2 ICT24024 7BC2M ICT24048 7BC2 ICT24048 7BC2M All m...

Page 2: ...uit breaker Ensure battery polarity is correct before connecting Do not attempt to charge a frozen battery Handle batteries with care do not short circuit battery terminals CAUTION Risk of personal in...

Page 3: ...charge rates to accommodate lower capacity batteries Wide range Power Factor corrected AC input supports operation world wide Floating Form C alarm contact output supports remote monitoring of unit o...

Page 4: ...LVD relay switches the BATT terminal Do not connect the battery to any other terminal AC input wiring to the charger must be protected using an outlet with a branch rated circuit breaker of 20A or low...

Page 5: ...urrent limit set by the BATT Switch settings 3 4 Use this setting if the connected load requires a non varying output voltage or if the backup battery is not used or if it does not need to be fast cha...

Page 6: ...arm output common Alarm Output Contacts Connect the optional remote battery temperature sensor ICT TMP to the TEMP input on the back panel removable connector Using the TMP sensor will enable the unit...

Page 7: ...l bypass critical internal circuitry disabling the charge control functions The internal LVD relay is in series with the BATT terminal Check that all connections to the charger are correct and tight r...

Page 8: ...e the display between output current and battery current measurements Each step of the bar graph represents a 10 increment in current Note that the display will turn off approximately 15 minutes after...

Page 9: ...ent has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules and ICES 003 These limits are designed to provide reasonable protection agains...

Page 10: ...2 4A 4 8A 2 4A 4 8A Idle DC Power Draw5 200mW 200mW 200mW 200mW 200mW 3 Stage Charge Parameters at 25 C Absorb V AGM 14 55 14 55 29 1 29 1 58 2 Flooded 14 4 14 4 28 8 28 8 57 6 Gel 14 2 14 2 28 4 28...

Page 11: ...ector 2 pins on 5 pin plug Operating Temperature Range 30C to 60 C6 Storage Temperature Range 40 to 70 C Humidity Operating 10 90 non condensing Storage 5 95 non condensing Cooling Temperature control...

Page 12: ...bsite at www ict power com support warranty repair The Purchaser shall at their own risk and cost return the defective product to ICT s factory or designated repair center once an RMA is issued by ICT...

Page 13: ...ermal or electrical stress improper maintenance or causes external to the unit including but not limited to general environmental conditions such as rust corrosive atmospheres sustained temperatures o...

Reviews: