ICT ICT24012-15BC2 Instruction Manual Download Page 11

 

Innovative Circuit Technology Ltd. 

11 

Alarm Output:   

Form-C contact, 0.5A 
60Vdc max 

 
DC Connectors: (Output, Battery) 

Terminal Block, M4 
Screws, 9mm spade max 
width 

 
Alarm Connector: 

3 pins on 5 pin removable 
plug, cage clamp type 16 

 

28AWG 

Bat Temp Sensor Connector: 

2 pins on 5 pin plug 

 
Operating Temperature Range: 

-30C to +60°C

6

 

 
Storage Temperature Range: 

-40 to +70°C 

 
Humidity: 

(Operating) 

10 

 90% (non-condensing) 

 

(Storage) 

 95% (non-condensing) 

 
Cooling: 

 

Temperature controlled 
fan 

Regulatory Compliance: 

Designed to meet 
UL/CSA60950-1, Meets 
FCC Part 15 Class B limits 

Dimensions (inches): 

 

Weight (lbs/kg): 

2.61lbs/1.19kg 

                                                 

6

 

De-rate output 1% per °C above 50°C

 

All manuals and user guides at all-guides.com

all-guides.com

Summary of Contents for ICT24012-15BC2

Page 1: ...00 Innovative Circuit Technology Ltd Models ICT24012 30BC2 ICT24012 30BC2M ICT24012 15BC2 ICT24012 15BC2M ICT24024 15BC2 ICT24024 15BC2M ICT24024 7BC2 ICT24024 7BC2M ICT24048 7BC2 ICT24048 7BC2M All m...

Page 2: ...uit breaker Ensure battery polarity is correct before connecting Do not attempt to charge a frozen battery Handle batteries with care do not short circuit battery terminals CAUTION Risk of personal in...

Page 3: ...charge rates to accommodate lower capacity batteries Wide range Power Factor corrected AC input supports operation world wide Floating Form C alarm contact output supports remote monitoring of unit o...

Page 4: ...LVD relay switches the BATT terminal Do not connect the battery to any other terminal AC input wiring to the charger must be protected using an outlet with a branch rated circuit breaker of 20A or low...

Page 5: ...urrent limit set by the BATT Switch settings 3 4 Use this setting if the connected load requires a non varying output voltage or if the backup battery is not used or if it does not need to be fast cha...

Page 6: ...arm output common Alarm Output Contacts Connect the optional remote battery temperature sensor ICT TMP to the TEMP input on the back panel removable connector Using the TMP sensor will enable the unit...

Page 7: ...l bypass critical internal circuitry disabling the charge control functions The internal LVD relay is in series with the BATT terminal Check that all connections to the charger are correct and tight r...

Page 8: ...e the display between output current and battery current measurements Each step of the bar graph represents a 10 increment in current Note that the display will turn off approximately 15 minutes after...

Page 9: ...ent has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules and ICES 003 These limits are designed to provide reasonable protection agains...

Page 10: ...2 4A 4 8A 2 4A 4 8A Idle DC Power Draw5 200mW 200mW 200mW 200mW 200mW 3 Stage Charge Parameters at 25 C Absorb V AGM 14 55 14 55 29 1 29 1 58 2 Flooded 14 4 14 4 28 8 28 8 57 6 Gel 14 2 14 2 28 4 28...

Page 11: ...ector 2 pins on 5 pin plug Operating Temperature Range 30C to 60 C6 Storage Temperature Range 40 to 70 C Humidity Operating 10 90 non condensing Storage 5 95 non condensing Cooling Temperature control...

Page 12: ...bsite at www ict power com support warranty repair The Purchaser shall at their own risk and cost return the defective product to ICT s factory or designated repair center once an RMA is issued by ICT...

Page 13: ...ermal or electrical stress improper maintenance or causes external to the unit including but not limited to general environmental conditions such as rust corrosive atmospheres sustained temperatures o...

Reviews: