PRODUCT DESCRIPTION
The
ICT180S-12B
Broadband Distribution Panel is designed for –48VDC applications. It provides 12
output positions that are individually protected by GMT type fuses and are rated up to 15A each. These
fuses are located on the front of the panel for easy monitoring and replacement. Each BAT (battery)
output terminal point is connected through a fuse to a BAT internal bus. All RTN (return) output
terminal points are connected to a RTN internal bus.
There are five alarm inputs on the back of the panel for connecting external Dry Contact sensors for
site monitoring and reporting of alarms such as door, water, and smoke detectors.
System voltage, system current, output currents, fuse status, and alarm input status can be monitored
onsite through the LCD graphics display. Fuse status is also displayed by an LED indicator located over
each fuse. Form “C” alarm contacts (C/NO/NC) are provided on the back of the panel which can be
connected to an external alarm circuit for monitoring alarms generated by the panel.
Remote monitoring is available through the integrated security protected Ethernet communications
port on the back of the panel. The panel has a built-in web server with an embedded web-based GUI
that can be accessed using any standard commercial web browser such as Internet Explorer. The web
server not only displays panel information, it can also be set up to send an alarm to user-defined
email accounts in the event a fault occurs. The web server can also be used for data logging of up to
30 days of time stamped event information. All these features are packaged in a 1RU enclosure to
save valuable rack space and fit standard 19” equipment racks. The rack mounting position is
adjustable.
FRONT PANEL
Figure 1.
1. FUSE STATUS LEDs: Turns on when a fuse is blown.
2. GMT FUSES: Location of the GMT fuses rated up to 15A.
3. LCD: Displays system voltage, system current, output current and fuse
status for each of the 12 output positions.
4. OUTPUT SELECT BUTTON: For switching between LCD screens, and resetting
network, web server and password settings to original factory default values.
5. GMT FUSES: Location of the GMT fuses rated up to 15A.
3