2.4.2 After the UPS starts up, verify that all three LED indicators on the front 
panel are illuminated.

2.4.3   Turn   on   the   battery   circuit   breaker   (handle   in   the   up   position).   The 
characteristic sound of the main transformer in the UPS may change somewhat 
due to charging of the battery system.

2.4.4 Connect the load(s) to the UPS output.

2.5      Continuous Operation

  

It is recommended that the unit be left on all the time. This will insure that the 
battery remain charged to it full capacity. The unit is designed to operate 24 
hours per day and is not required that it be turned off during the week-ends

2.6      Shut Down Procedure

2.6.1 Disconnect the load from the UPS.

2.6.2 Disconnect the commercial AC source from the UPS.

2.6.3 Press the BATTERY OFF push-button switch on the front panel to turn off 
the UPS.

2.6.4   Turn   off   the   BATTERY   CIRCUIT   BREAKER     (handle   in   the   down 
position) to prevent further discharge of the battery.

2.6.5 If servicing of the UPS or the battery is required, disconnect the battery 
cable at the battery before performing any maintenance.

3.        DESCRIPTION OF OPERATION

3.1

General Operation

Figures 3.1 and 3.2 illustrate the operation of this system.   Please note that 
under normal operation (Figure 3.1), the AC input operates through the inverter 
and is then further regulated and filtered.  The output of the unit is a very clean 
sinewave with an output voltage that is regulated to  3% with an input 
voltage swing of + 10% and -15%.   During this operation, a special inverter 
circuit provides trickle charge to the battery.

During standby operation when the commercial line is not present, the inverter 
is switched totally to the battery which converts the battery’s DC voltage to AC 
and supplies power to the regulator/filter.  The output is then the same as if the 
line   were   present.   Transfer   from   a   charger   to   inverter   is   done   within 
microseconds and no power interruption occurs at the output.

4

Summary of Contents for Lifeline M95-600 Series

Page 1: ...NINTERRUPTIBLE POWER SYSTEM MODEL M95 600 SERIES PART NO 9300057 DRAWING NO 8060180 ISSUED 5 21 07 REV B RELEASED INSTRUMENTATION AND CONTROL SYSTEMS INC 520 WEST INTERSTATE ROAD ADDISON ILLINOIS 6010...

Page 2: ...ny situation develops that is different from what is described herein contact the factory for further assistance 1 3 Proprietary Notice This equipment was designed and manufactured under several paten...

Page 3: ...s This UPS is provided with external batteries which must be connected to the unit Confirm that all sources of power are off and that the battery circuit breaker on the left side of the cabinet is off...

Page 4: ...in the down position to prevent further discharge of the battery 2 6 5 If servicing of the UPS or the battery is required disconnect the battery cable at the battery before performing any maintenance...

Page 5: ...LOAD PRESENT STATIC SWITCH CLOSED BATTERY CHARGER Figure 3 1 Commercial Power On 3 3 Operation From Battery During the loss of commercial AC power the battery provides DC current to the inverter which...

Page 6: ...he factory However if any adjustments need to be made it is probably due to component changes in the field over a long period of time Under those circumstances it is important that the user contact th...

Page 7: ...t when commercial power is present X No AC output when commercial power is not present X Check Battery Battery does not charge X X Check Battery Output voltage low X Reduce Load Output frequency low o...

Page 8: ...s well as all shipping cost On repaired apparatus the warranty shall be as for new apparatus except that it shall only apply to the parts repaired or replaced by ICS Inc No separate warranty shall app...

Page 9: ...ns and other consequential damages whether direct or indirect and whether or not resulting from or contributed to by the default or negligence of ICS Inc its agent employees and sub contractors which...

Page 10: ...ature 10 to 40 degrees C Operating Humidity 0 to 85 non condensing Storage Temperature 0 to 65 degrees C Input Output Connections Terminal strip with provisions for conduit entry 6 2 Controls Battery...

Page 11: ...BATTERY WIRES 8GA AWG MIN ALL OTHER WIRES 18GA AWG MIN TOTAL UPS LOAD WITH BATTERY BACKUP 5AAC MAX 2 HOURS BACKUP TIME AT 5 0 AAC OUTPUT 4 HOURS BACKUP TIME AT 2 5AAC OUTPUT CONNECT TO EARTH GROUND 11...

Page 12: ...CABINET DIMENSIONS 12...

Page 13: ...P INPUT OUTPUT CONNECTION ACCESS 4 DUAL CONCENTRIC CONDUIT HOLES OPERATING TEMPERATURE 10 40 DEGREES C OPERATING HUMIDITY 0 85 NON CONDENSING STORAGE TEMPERATURE 0 65 DEGREES C 4 CONTROLS BATTERY CIRC...

Page 14: ...ted 3 3 Turn on battery circuit breaker handle up The characteristic sound of the main transformer in the UPS may change somewhat due to charging of the battery system 3 4 Connect the load s to the UP...

Reviews: