INTRODUCTION

1.1

System Description

Thank you for purchasing one of the LIFELINE series of Uninterruptible Power 
Systems manufactured by Instrumentation & Control Systems Inc., Electropac 
Division. The particular UPS described by this manual, part number 9300057, 
represents the latest in efficient, clean and highly reliable source of AC power. 
In the line regulated mode, the system provides regulated AC output with a 
maximum of efficiency and minimum of noise. Coupled with the battery, the 
UPS   gives   the   user   protection   from   disruption   of   power   to   the   critical 
equipment.

1.2

Manual Description

The purpose of this manual is to provide the user with installation, operation 
and maintenance of the LIFELINE Uninterruptible Power System,  part number 
9300057.   This   manual   should   be   read   thoroughly   to   familiarize   personnel 
before the system is operating. If any situation develops that is different from 
what is described herein, contact the factory for further assistance.

1.3

Proprietary Notice

This equipment was designed and manufactured under several patents owned 
by   ICS,   Inc.   The   user   of   these   patented   circuits   or   reproductions   of   the 
drawings, schematics, etc. may not occur except by written permission from 
ICS, Inc.

1.4

HAZARD CAUTION

The normal operating voltages contained within the cabinet are as much as 
600 volts. It is extremely important that caution be exercised when working on 
this equipment. 

When connecting DC terminals to the external batteries, it is very important that 
correct polarity be observed.

2.

Standard Installation

2.1

Unpacking

Carefully   unpack   the   unit   and   remove   any   packing   materials.   Inspect   the 
cabinet and the front panel controls. Remove the two screws near the right 
edge of the front panel and open the door of the unit . Inspect the interior of the 
unit     for   possible   damage   or   dislodging   of   components.   Retain   packing 
materials to return unit if operational problems occur.

2

Summary of Contents for Lifeline M95-600 Series

Page 1: ...NINTERRUPTIBLE POWER SYSTEM MODEL M95 600 SERIES PART NO 9300057 DRAWING NO 8060180 ISSUED 5 21 07 REV B RELEASED INSTRUMENTATION AND CONTROL SYSTEMS INC 520 WEST INTERSTATE ROAD ADDISON ILLINOIS 6010...

Page 2: ...ny situation develops that is different from what is described herein contact the factory for further assistance 1 3 Proprietary Notice This equipment was designed and manufactured under several paten...

Page 3: ...s This UPS is provided with external batteries which must be connected to the unit Confirm that all sources of power are off and that the battery circuit breaker on the left side of the cabinet is off...

Page 4: ...in the down position to prevent further discharge of the battery 2 6 5 If servicing of the UPS or the battery is required disconnect the battery cable at the battery before performing any maintenance...

Page 5: ...LOAD PRESENT STATIC SWITCH CLOSED BATTERY CHARGER Figure 3 1 Commercial Power On 3 3 Operation From Battery During the loss of commercial AC power the battery provides DC current to the inverter which...

Page 6: ...he factory However if any adjustments need to be made it is probably due to component changes in the field over a long period of time Under those circumstances it is important that the user contact th...

Page 7: ...t when commercial power is present X No AC output when commercial power is not present X Check Battery Battery does not charge X X Check Battery Output voltage low X Reduce Load Output frequency low o...

Page 8: ...s well as all shipping cost On repaired apparatus the warranty shall be as for new apparatus except that it shall only apply to the parts repaired or replaced by ICS Inc No separate warranty shall app...

Page 9: ...ns and other consequential damages whether direct or indirect and whether or not resulting from or contributed to by the default or negligence of ICS Inc its agent employees and sub contractors which...

Page 10: ...ature 10 to 40 degrees C Operating Humidity 0 to 85 non condensing Storage Temperature 0 to 65 degrees C Input Output Connections Terminal strip with provisions for conduit entry 6 2 Controls Battery...

Page 11: ...BATTERY WIRES 8GA AWG MIN ALL OTHER WIRES 18GA AWG MIN TOTAL UPS LOAD WITH BATTERY BACKUP 5AAC MAX 2 HOURS BACKUP TIME AT 5 0 AAC OUTPUT 4 HOURS BACKUP TIME AT 2 5AAC OUTPUT CONNECT TO EARTH GROUND 11...

Page 12: ...CABINET DIMENSIONS 12...

Page 13: ...P INPUT OUTPUT CONNECTION ACCESS 4 DUAL CONCENTRIC CONDUIT HOLES OPERATING TEMPERATURE 10 40 DEGREES C OPERATING HUMIDITY 0 85 NON CONDENSING STORAGE TEMPERATURE 0 65 DEGREES C 4 CONTROLS BATTERY CIRC...

Page 14: ...ted 3 3 Turn on battery circuit breaker handle up The characteristic sound of the main transformer in the UPS may change somewhat due to charging of the battery system 3 4 Connect the load s to the UP...