OPERATING INSTRUCTIONS FOR UPS PART NO. 9300057

DRAWING N0. 8060181
ISSUED 06/16/94
REV. A: RELEASED

Mount this sheet in a frame and locate it adjacent to the unit. Refer to Drawing/Manual No. 8060180, issued 

06/16/94 for complete information.

1. Ratings:
    Input AC Power: 120VAC, 60Hz., 8AAC nominal
    Input DC Power: 48VDC, 55AH Battery
    Output AC Power:120VAC, 60Hz., 5AAC
    Charging Current: 2ADC

2. Intended Load: Fire Protection Signaling Systems

3. Startup Procedure
    3.1 With the battery circuit breaker off (handle in down position) and the load(s) disconnected, apply AC
          input power.
    3.2 After UPS starts up, verify that all three LED indicators on front panel are illuminated.
    3.3 Turn on battery circuit breaker (handle up). The characteristic sound of the main transformer in the 
          UPS may change somewhat due to charging of the battery system.
    3.4 Connect the load(s) to the UPS output.

4. Shutdown Procedure
    4.1 Disconnect the load(s) from the UPS.
    4.2 Disconnect the commercial AC power source from the unit.
    4.3 Press the BATTERY OFF pushbutton switch on the front panel to turn off the UPS.
    4.4 Turn off the battery circuit breaker (handle in the down position) to prevent further discharge of the 
          battery.
    4.5 If further servicing of the UPS or battery system is required, disconnect the battery cables at the 
          battery before performing any maintenance.

5. Local Service Representative:

        Name:

    Address:

          TEL:

                               FAX:

INSTRUMENTATION & CONTROL SYSTEMS INC. 

520 WEST INTERSTATE ROAD ADDISON, ILLINOIS 60101 USA

TEL (630) 543-6200 FAX (630) 543-6244

14

Summary of Contents for Lifeline M95-600 Series

Page 1: ...NINTERRUPTIBLE POWER SYSTEM MODEL M95 600 SERIES PART NO 9300057 DRAWING NO 8060180 ISSUED 5 21 07 REV B RELEASED INSTRUMENTATION AND CONTROL SYSTEMS INC 520 WEST INTERSTATE ROAD ADDISON ILLINOIS 6010...

Page 2: ...ny situation develops that is different from what is described herein contact the factory for further assistance 1 3 Proprietary Notice This equipment was designed and manufactured under several paten...

Page 3: ...s This UPS is provided with external batteries which must be connected to the unit Confirm that all sources of power are off and that the battery circuit breaker on the left side of the cabinet is off...

Page 4: ...in the down position to prevent further discharge of the battery 2 6 5 If servicing of the UPS or the battery is required disconnect the battery cable at the battery before performing any maintenance...

Page 5: ...LOAD PRESENT STATIC SWITCH CLOSED BATTERY CHARGER Figure 3 1 Commercial Power On 3 3 Operation From Battery During the loss of commercial AC power the battery provides DC current to the inverter which...

Page 6: ...he factory However if any adjustments need to be made it is probably due to component changes in the field over a long period of time Under those circumstances it is important that the user contact th...

Page 7: ...t when commercial power is present X No AC output when commercial power is not present X Check Battery Battery does not charge X X Check Battery Output voltage low X Reduce Load Output frequency low o...

Page 8: ...s well as all shipping cost On repaired apparatus the warranty shall be as for new apparatus except that it shall only apply to the parts repaired or replaced by ICS Inc No separate warranty shall app...

Page 9: ...ns and other consequential damages whether direct or indirect and whether or not resulting from or contributed to by the default or negligence of ICS Inc its agent employees and sub contractors which...

Page 10: ...ature 10 to 40 degrees C Operating Humidity 0 to 85 non condensing Storage Temperature 0 to 65 degrees C Input Output Connections Terminal strip with provisions for conduit entry 6 2 Controls Battery...

Page 11: ...BATTERY WIRES 8GA AWG MIN ALL OTHER WIRES 18GA AWG MIN TOTAL UPS LOAD WITH BATTERY BACKUP 5AAC MAX 2 HOURS BACKUP TIME AT 5 0 AAC OUTPUT 4 HOURS BACKUP TIME AT 2 5AAC OUTPUT CONNECT TO EARTH GROUND 11...

Page 12: ...CABINET DIMENSIONS 12...

Page 13: ...P INPUT OUTPUT CONNECTION ACCESS 4 DUAL CONCENTRIC CONDUIT HOLES OPERATING TEMPERATURE 10 40 DEGREES C OPERATING HUMIDITY 0 85 NON CONDENSING STORAGE TEMPERATURE 0 65 DEGREES C 4 CONTROLS BATTERY CIRC...

Page 14: ...ted 3 3 Turn on battery circuit breaker handle up The characteristic sound of the main transformer in the UPS may change somewhat due to charging of the battery system 3 4 Connect the load s to the UP...

Reviews: