6 Set up with the display and adjustment module
WIKA Operating Instructions - Process pressure transmitter IPT-2x
In menu item "
Scaling (2)
" you define the scaling format on the display
and the scaling of the measured level value for 0 % and 100 %.
In menu item "
Current output, variable
" you specify which measured
variable is output via the current output.
Depending on the selected measured variable, you assign in the
menu item "
Current output, adjustment
" the measured values that
4 mA (0 %) and 20 mA (100 %) of the current output refer to.
If the measuring cell temperature is selected as measured variable,
then e.g. 0 °C refers to 4 mA and 100 °C to 20 mA.
In this menu item you gain access to the protected area where
you can enter special parameters. In exceptional cases, individual
parameters can be modified in order to adapt the sensor to special
requirements.
Change the settings of the special parameters only after having con-
tacted our service staff.
6.4.5 Info
In this menu item, you can read out the instrument name and the
instrument serial number:
Scaling (2)
Current output (meas.
variable)
Current output (adjust-
ment)
Special parameters
Device name