Connecting Input Power 

 

IMPORTANT: 

It is good practice to turn off input and load power, and unplug the power 

terminal block before making wire connections. Otherwise, your screwdriver blade can 

inadvertently short your terminal connections to the grounded enclosure. 

 
 
 
 

Identify PWR1, GND, PWR2, GND contacts on terminal block. Then identify 

power wire and ground wire. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Insert the wire of your DC supply or Battery supply into the PWN1 and/or 

PWN2 contacts of the terminal block connector, and fastening the terminal 

screws to prevent the wires from coming loose. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

NOTE: 

For best reliability, please install both of PWN1 and PWN2 for power redundant. 

 
 
 
 
 
 

 

TDRS4050601 

20 

Summary of Contents for RS Series

Page 1: ...TM RS Series User Manual Industrial Redundant Ring Switch Version 1 2 This document applied to models of RS 405 405F 405A 405AF 408 408A RSM 405 405F 405 R 405AF 408 408A ...

Page 2: ...Industrial Redundant Ring Switch RS Series User Manual Revision History Revision Date 1 0 2006 07 01 1 1 2012 03 22 1 2 2021 11 11 i TDRS4050601 ...

Page 3: ...red in a retrieval system or transmitted in any form or by any means whether electronic mechanical photo copying recording or otherwise without the prior written permission of the publisher The names used for identification only may be registered trademarks of their respective companies Copyright ICP DAS Co Ltd All Rights Reserved TDRS4050601 ii ...

Page 4: ...tandards The Ring Switch meets the following standards EMCimmunity IEC61326 1 IEEE C37 90 EMI emissions FCC part 15 ICES 003 EN55022 Class B Electrical safety UL 508 CSA C22 14 EN61010 1 IEC1010 Warning ICP DAS assume no liability for damages consequent to the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is bel...

Page 5: ...or automation and control engineers who have been forced into this IT domain they really don t want to get too involved with the idiosyncrasies and maintenance of Ethernet networks To satisfy these the RS Series Switch provides you a rugged fault tolerant plug and play solution ICP DAS industrial Switch Series ICP DAS industrial Ethernet switch has the following series NS Series Network Switch Ser...

Page 6: ...nce 9 Dimensions Units mm 10 Dimensions Units mm 10 Rotary Switch SW2 16 Hardware Installation 17 DIN Rail Mounting Installation 18 Wall Mounting Installation 18 Wall Mounting Installation 19 Connecting Input Power 19 Connecting Input Power 20 Connecting Output Relay 21 Connecting Ethernet Ports 21 Connecting Ethernet Ports 22 Connecting Fiber Ports only for models with fiber port 23 Configuration...

Page 7: ...rts for cmask command bb Table 4 Assign mask value for activating relay output when there is communication loss occurring on the port s bb Table 5 Assign mask value for system status relay output gg Table 6 Corresponding bits and ports for lvalue gg Table 7 Clarify current link status by returned lvalue gg Table 8 Corresponding bits and ports for cvalue ll Table 9 Clarify current link status by re...

Page 8: ...Acronym for Carrier Sense Multiple Access with Collision Detection Access protocol for Ethernet CSU Acronym for Channel Service Unit a device furnished as an integral part of a digital access line where a user wishes to supply the bipolar signals It provides the network with protection against user side electrical anomalies such as surges and provides the user with network clocking CTS Acronym for...

Page 9: ...Acronym for Field Programmable Gate Array LAN A local area network is a group of PCs connected over a common medium within a building MAC Acronym for Medium Access Control A designated hardware address for each device on a LAN or MAN This address is burnt into The network interface card NIC by its manufacturer MAN A metropolitan area network is a group of PCs connected over a common medium within ...

Page 10: ...rminating equipment employing serial binary data interchange RS 485 Standard defined by EIA aka EIA 485 Standard for electrical characteristics of generators and receivers for use in balanced multipoint systems RTS Acronym for Request To Send SCADA Acronym for Supervisory Control and Data Acquisition SNMP Acronym for Simple Network Management Protocol A standard management protocol used to provide...

Page 11: ...itch Overview The RS Series Industrial Redundant Ring Switch is designed upon concepts of reliability quick recovery easy configuration self healing and SCADA for status monitoring Besides all models in RS Series mechanism is also designed to meet IP301 above for working under harsh environment Unlike other existing ring switch or managed Ethernet switch on the market the RS Series is much more ea...

Page 12: ...one system is allowed to proceed with a transmission of a frame within a Collision Domain at any one time This is a major disadvantage when using Hubs and Repeaters within a network A switch like a hub has to forward and receive packets from one network or device to another The switch could forward all packets but if this was the case it would have similar behaviour to a hub It would be more intel...

Page 13: ...ate propriety protocols that enable multiple Switches to be placed into a redundant ring A single Switch configured as the network focal point will monitor detect and recover from a fiber or copper link failure within approximately 50mS for the majority of applications a seamless process The configuration process of the network focal point is simple as it must be remembered that as the switches ar...

Page 14: ...reasingly popular over the past decade A basic fiber optic system using an optical transceiver circuit and fiber optic media offers a wide array of benefits that are not available with traditional copper conductors Advantages of Fiber Optic Data Transmission Technology High data rate and wide bandwidth Immunity to EMI RFI and lightning damage No ground loops Low attenuation data loss Longer distan...

Page 15: ...ies of industrially hardened fiber optic communication products addresses these issues and provides you with optimal solutions for your factory automation and process control needs RS Series Key Features Connectors locate in front panel reducing wiring complexity and easy maintenance Dual input power supply for non stop connectivity Patent pending Cyber Ring Protocol Versatile DIN rail surface and...

Page 16: ...rs with industrial plastic case Overview The RS Series is designed for easy installation configuration and maintenance For hardware installation we provide both easy DIN rail mounting and wall mounting modes To establish a simple redundant ring only 2 jumpers on the front panel to set to form a ring It does not depend on web configuration interface neither a management server All of connectors are...

Page 17: ...Industrial Redundant Ring Switch RS Series User Manual Dimensions Units mm TDRS4050601 10 ...

Page 18: ...Industrial Redundant Ring Switch RS Series User Manual 11 TDRS4050601 ...

Page 19: ...per 2 Reset to default jumper 3 Primary Secondary Switch setting jumper 4 Ring protocol selecting jumper 5 Enabling Ring 2 jumper 6 Enabling Ring 1 jumper Rotate jumper block Serial port Terminal block 1 Frame Ground F G 2 Relay R NO 3 Relay R COM 4 Power 2 Grounding GND 5 Power 2 PWR2 6 Power 1 Grounding GND 7 Power 1 PWR1 Interconnection port for 2 phase recovering coupling RJ 45 Ethernet ports ...

Page 20: ...o default jumper 3 Primary Secondary Switch setting jumper 4 Ring protocol selecting jumper 5 Enabling Ring 2 jumper 6 Enabling Ring 1 jumper Rotate jumper block Serial port Terminal block 1 Frame Ground F G 2 Relay R NO 3 Relay R COM 4 Power 2 Grounding GND 5 Power 2 PWR2 6 Power 1 Grounding GND 7 Power 1 PWR1 Interconnection port for 2 phase recovering coupling RJ 45 Ethernet ports Fiber Ports 1...

Page 21: ...LED indicator Switch jumper block 1 Ring Normal Switch selecting jumper 2 Reset to default jumper 3 Primary Secondary Switch setting jumper 4 Ring protocol selecting jumper 5 Enabling Ring 2 jumper 6 Enabling Ring 1 jumper RJ 45 Ethernet ports Terminal block Rotate jumper block Interconnection port for 2 phase recovering coupling TDRS4050601 14 ...

Page 22: ...n of DIP and Rotate jumpers setting value Quick Config Guide has been printed on both right and left hand side of front panel After acquainted with RS Series features field engineers could deploy switches quickly by referencing Quick Config Guide RS M 405 408 series RSM 405 R series 15 TDRS4050601 ...

Page 23: ...air 1 Enable Ring Pair 1 Rotary Switch SW2 Rotary SW position F E D C B A 9 8 Recovery Time 1 5s 1 4s 1 3s 1 2s 1 1s 1 0s 900 ms 800 ms Forwarding Delay 30s 28s 26s 24s 22s 20s 18s 16s Hello Time 10s 10s 10s 10s 10s 10s 10s 10s Max Age 40s 40s 40s 40s 40s 38s 34s 30s Rotary SW position 7 6 5 4 3 2 1 0 Recovery Time 700 ms 600 ms 500 ms 400 ms 300 ms 200 ms 100 ms N A Forwarding Delay 14s 12s 10s 8...

Page 24: ...n Wall Mounting Installation Connecting Input Power Connecting Output Relay Connecting Ethernet Ports Connecting Fiber Ports and wall mounting modes Overview RS Series support redundant power output relay and enhanced isolation to make device much robust With ICP DAS patent DIN Clip design the installation is just as easy as plugging power cord into outlet 17 TDRS4050601 ...

Page 25: ...ation becomes very easy Following 3 steps completes installation Pull the down rail clip out Up Clip Down Clip Push Clip Obliquing the switch and insert the upper rail clips onto the upper lip of the DIN rail track Then push down the switch to fit into DIN rail as shown below Push up down rail clip to lock the switch on the DIN rail TDRS4050601 18 ...

Page 26: ... design Wall Mounting installation becomes very easy Following 2 steps completes installation Pull out Pull out Pull all wall mounting clip out Use the slotted holes at each corner of the wall mounting clip to attach the unit to the wall or other flat surface Then fasten it on the wall with screw 19 TDRS4050601 ...

Page 27: ...vertently short your terminal connections to the grounded enclosure Identify PWR1 GND PWR2 GND contacts on terminal block Then identify power wire and ground wire Insert the wire of your DC supply or Battery supply into the PWN1 and or PWN2 contacts of the terminal block connector and fastening the terminal screws to prevent the wires from coming loose NOTE For best reliability please install both...

Page 28: ...nnecting Output Relay The diagram of output relay Identify R NO and R COM contacts on terminal block Insert the relayed device such as a light bulb or a buzzer pair of wire and fastening the terminal screws to prevent the wires from coming loose 21 TDRS4050601 ...

Page 29: ...s shown in the table below Connect one side of an Ethernet cable into any switch port and connect the other side to your attached device The green LNK LED will light up when the cable is correctly connected Always make sure that the cables between the switches and attached devices e g switch hub or workstation are less than 100 meters 328 feet Two switches are now up linked together If we change t...

Page 30: ...C type connectors in multi mode and single mode versions The following table describes the Fiber Ports LEDs State Color ON OFF BLINK P1_Link Link Not Link Transmission P2_Link Link Not Link Transmission RS Switch offer a relay contact output on Terminal Block of the Switch equipment refer page 18 It is able to connect to a light buzzer etc warning device and notify system failures immediately conf...

Page 31: ...ur demand One Ring Topology Two Rings Coupling Two Rings Coupling with Two Phase Recovering Overview To successfully form a robust industrial Ethernet network the designing of network pattern is the most important stage A well designed network pattern could dramatically reduce the risk network failure in critical situation TDRS4050601 24 ...

Page 32: ...e have formed a ring network the focal point master will choose any one and only one path as Redundant Path It is actually inactive when the ring network works properly At the moment of any connection failure the focal point will activates the Redundant Path and fire alarm to output relay Backup Path Active Path Broken RS Series come with 2 ring pair by default A ring pair can form a ring with oth...

Page 33: ... Redundant Ring Switch RS Series User Manual Two Rings Coupling As a ring network is a small group of switches by geography functionalities or subsystem 2 or more rings could be coupled together to form a whole picture of industrial network for an integrated system Single coupling point uses a switch to bridge 2 rings Each ring still keeps original ring topology features 6 5 4 3 2 1 Jumper O F F F...

Page 34: ...n OFF 6 5 4 3 2 1 Jumper 6 F O F F F F On OFF O 6 5 4 3 2 1 Jumper F O F F F F On OFF 6 5 4 3 2 1 Jumper F O F O F F On OFF 6 5 4 3 2 1 Jumper O F F F F F On OFF 6 5 4 3 2 1 Jumper O F F F F F On OFF 6 5 4 3 2 1 Jumper F O F F F F On OFF 6 5 4 3 2 1 Jumper 6 5 4 3 2 1 Jumper F O F F F F On OFF O F F F F F On OFF 6 5 4 3 2 1 Jumper F O F F F F On OFF 6 5 4 3 2 1 Jumper F O F O F F On OFF 6 5 4 3 2 ...

Page 35: ...ing Overview No Power to the Switch No Link Light on a Switch Port Master LED Keep on Flashing This chapter includes some information for general troubleshooting as follows No Power to the Switch No Link Light on a Switch Port Master LED Keep on Flashing TDRS4050601 28 ...

Page 36: ...aster LED keep on Flashing Check if Jumper 1 on SW1 is switched to Tradition mode ON if you intend to use tradition mode keep this setting Do not restart If you would like to use redundancy mode switch Jumper 1 to OFF and restart the switch Check if the topology is accurate C hec k if network is functioning properly Check if power supply is connected properly Check if there is devices failure exit...

Page 37: ...ll On line support HTTP WWW ICPDAS COM TW SEVICES SUPPORT HTM E MAIL SUPPORT ICPDAS COM Contact Worldwide TELEPHONE FAX Taiwan Hsinchu Headquarter 886 3 5973366 886 3 5973733 Banchiao Office 886 2 29500655 886 2 29500807 Hsintien Office 886 2 89192220 886 2 89192221 Taichung Office 886 4 23582815 886 4 23589114 Kaoshiung Office 886 7 2157688 886 7 2162602 USA USA Office 1 310 517 9888 x101 1 310 5...

Page 38: ...th one or more conductors where all devices are able to receive all transmissions at the same time Counter Rotating Ring Aka Self Healing Ring has two physical transmission lines or rings with transmitting and receiving signals in each ring travelling in opposite directions If the line or a device along the ring fails the ring re anneals by bypassing the device and or line and forms with the other...

Page 39: ...microprocessor Node A network connected device such as a server or PC Order Wire Voice channel used to communicate between two locations Packet A grouping of data usually consisting of data and an address header prior to being sent over a network Point of Presence POP The physical access location within a specific location of the long distance or common carrier Polling The method used for terminal...

Page 40: ...s passed from station to station in sequential order The stations wishing to access must wait for the token before transmitting data in the token ring the next logical station is also the next physical station Virtual Path A software controlled point to point connection between two devices or segments c TDRS4050601 ...

Page 41: ...tage Range 10 30 VDC Isolation redundant input 12 48 VDC Non Isolation redundant input Power Consumption 0 22 A 24 VDC 5 arrowed with 100M Full duplex Protection Power reverse polarity protection Frame Ground for EMS Protection Yes Connection 7 Pin Removable Terminal Block 5 Pin Removable Terminal Block Mechanical Casing Plastic Metal Plastic Metal Metal Environmental Rating UL 94V 0 IP30 Protecti...

Page 42: ...nside Non isolation Connection Yes Power Input Input Voltage Range 10 30 VDC Isolation redundant input 12 48 VDC Non Isolation Power Consumption 0 3 A 24 VDC 5 arrowed with 100M Full duplex Protection Power reverse polarity protection Frame Ground for EMS Protection Yes Connection 7 Pin Removable Terminal Block Mechanical Casing Plastic Metal Plastic Metal Environmental Rating UL 94V 0 Dimensions ...

Page 43: ...thernet 2 pair UTP STP Cat 3 4 5 EIA TIA 568 100 ohm Fast Ethernet 2 pair UTP STP Cat 5 EIA TIA 568 100 ohm Multi Mode Multi Mode Fiber Cables 50 125 62 5 125 or 100 140 µm Distance 2 km 62 5 125 µm recommended for full duplex Wavelength 1300 or 1310 nm Min TX Output 20 dBm Max TX Output 14 dBm Max RX Sensitivity 32 dBm Max RX Overload 8 dBm Budget 12 dBm Single Mode Standard Single mode fiber cab...

Page 44: ... arrowed Protection Power reverse polarity protection Frame Ground for EMS Protection Yes Connection 7 Pin Removable Terminal Block Mechanical Casing Plastic Metal Plastic Metal Environmental Rating UL 94V 0 IP30 Protection UL 94V 0 IP30 Protection Dimensions W x L x H 64 mm x 98 mm x 110 mm 72 5 mm x 102 mm x 110 mm 64 mm x 98 mm x 110 mm 72 5 mm x 102 mm x 110 mm Installation DIN Rail Mounting D...

Page 45: ... is forwarding 10032 Port 9 is forwarding 10025 Port 2 is forwarding 10033 Port 10 is forwarding 10026 Port 3 is forwarding 10034 Port 11 is forwarding 10027 Port 4 is forwarding 10035 Port 12 is forwarding 10028 Port 5 is forwarding 10036 Port 13 is forwarding 10029 Port 6 is forwarding 10037 Port 14 is forwarding 10030 Port 7 is forwarding 10038 Port 15 is forwarding 10031 Port 8 is forwarding 1...

Page 46: ...lue svalue hmivalue rtime time ftime time mtime time htime time com1 baudrate databit parity stopbit com2 baudrate databit parity stopbit help command Description Both help and display a list of available commands if parameter is not specified The command parameter is used to see detail information for a specific command Parameters Parameter Description command Please provide the name of the comma...

Page 47: ...Industrial Redundant Ring Switch RS Series User Manual Example reset Description The reset command will initiate Ring Switch a self restart All current setting values remain intact TDRS4050601 j ...

Page 48: ...to factory default values Current factory default values are as follow COM1 baudrate 115200 8bit none patity check 1 stopbit COM2 baudrate 115200 8bit none patity check 1 stopbit link mask 0 communication mask 0x1f status mask 0x3 netid 1 mac factory set unique MAC address ip 192 168 255 1 mask 255 255 255 0 Example k TDRS4050601 ...

Page 49: ...k or setmask command will display current mask address To assign a mask address for TCP IP please input mask address in the form of m1 m2 m3 m4 each field contains a value in the range 0 255 Example gateway setgateway Description If no gateway IP address is specified the gateway or setgateway command will display current gateway address Note that if there exits a check sum error an error message w...

Page 50: ... MAC address DO NOT change this address unless you have a good reason to do so If you do change the address remember to make a note of this factory set MAC address and keep it in a safe place netid id number Description If Net ID of Modbus is not specified the netid command will display current ID number of Modbus The command parameter id number is used to assign a specific ID number for Modbus Ne...

Page 51: ...ase refer to Appendix G Table 2 Parameters Parameter Description mask value Provides the mask value that you want to specify to configure status of relay when link loss occurs Example cmask mask value Description This command enables you to configure relay output activation status when there is communication loss occurring on port s The ports are corresponding to the 8 mask bits bit 0 corresponds ...

Page 52: ...on Power s or when the switch is selected as master switch the corresponding relay output will be activated The mask value is in hexadecimal format that represents the 8 bits corresponding binary numbers it can be either in the form of initiating 0X plus a suffix of the hexadecimal number or eliminating 0X simply the hexadecimal number itself If a mask value is not specified the smask command will...

Page 53: ...ication status showing by a hexadecimal number that represents the 8 bits corresponding binary numbers Bit 0 corresponds to port 1 etc Please refer to Appendix G Table 8 If there is a communication loss occurring on port s the corresponding bit s will be set up as 1 You would be able to clarify current communication status by this returned cvalue in hexadecimal format please refer to Appendix G Ta...

Page 54: ...n 0 you would be able to set up specific values for recovery time rtime forward delay ftime maximum age mtime and hello time htime manually If the position is on positions other than 0 1 to F a set of preset values will be applied The returned RotarySW value indicates the current position of SW2 Please refer to Appendix G Table 15 and sections of rtime ftime mtime and htime for more detail informa...

Page 55: ...he spanning tree bridge forward delay in milliseconds ms Forward delay is the time interval spent waiting to change a port from its spanning tree pre forwarding state to a forwarding state This is necessary because every bridge on the network should ensure no loop is formed before allowing the port to forward packets To setup the forward time manually you are required to switch the SW1 Jumper 4 to...

Page 56: ...e Provides the time interval ms that you want to set up as the maximum time Example htime time Description This command enables you to set the spanning tree bridge hello time in millisecond ms Hello time is the interval between transmission of spanning tree configuration messages All bridges send configuration messages during reconfiguration to select the designated root bridge in this case the sw...

Page 57: ...600 and 115200 The port speed and device speed must match The number of data bits can be 7 for true ASCII or 8 for any kind of data as this matches the size of a byte The parity check code can be set to none 0 even 1 or odd 2 None 0 means that no parity bit is sent at all Even 1 means applying even parity check each set of transmitted bits must have an even number of set bits Odd 2 means applying ...

Page 58: ...de can be set to none 0 even 1 or odd 2 None 0 means that no parity bit is sent at all Even 1 means applying even parity check each set of transmitted bits must have an even number of set bits Odd 2 means applying odd parity check each set of transmitted bits must have an odd number of set bits Stop bit is used in asynchronous communications to indicate the end of a piece of data Parameters Parame...

Page 59: ...otected against solid objects up to 2 5mm 4 Protected against solid objects up to 1mm 5 Protected against dust limited ingress no harmful deposit 6 Totally protected against dust Second Number 0 No protection Sometimes X 1 Protection against vertically falling drops of water e g condensation 2 Protection against direct sprays of water up to 15 degrees from vertical 3 Protection against direct spra...

Page 60: ...put Range 100 250AC Input Frequency 50Hz to 60 Hz Output 24Vdc 1Amp max Output Power 25Watts Operating Temperature 0 to 70 Storage Temperature 40 to 85 Demension 65 x 105 x 36mm KA 52F 68 x 107 x 50mm DIN KA52F Part No Information KA 52F 24V 1A output power supply DIN KA52F 24V 1A output power supply with DIN Rail Mount w TDRS4050601 ...

Page 61: ...0001001 0X9 or 9 2 or 4 00001010 0Xa or a 1 or 2 or 4 00001011 0Xb or b 3 or 4 00001100 0Xc or c 1 or 3 or 4 00001101 0Xd or d 2 or 3 or 4 00001110 0Xe or e 1 or 2 or 3 or 4 00001111 0Xf or f 5 00010000 0X10 or 10 1 or 5 00010001 0X11 or 11 2 or 5 00010010 0X12 or 12 1 or 2 or 5 00010011 0X13 or 13 3 or 5 00010100 0X14 or 14 1 or 3 or 5 00010101 0X15 or 15 2 or 3 or 5 00010110 0X16 or 16 1 or 2 or...

Page 62: ... or 41 2 or 7 01000010 0X42 or 42 1 or 2 or 7 01000011 0X43 or 43 3 or 7 01000100 0X44 or 44 1 or 3 or 7 01000101 0X45 or 45 2 or 3 or 7 01000110 0X46 or 46 1 or 2 or 3 or 7 01000111 0X47 or 47 4 or 7 01001000 0X48 or 48 1 or 4 or 7 01001001 0X49 or 49 2 or 4 or 7 01001010 0X4a or 4a 1 or 2 or 4 or 7 01001011 0X4b or 4b 3 or 4 or 7 01001100 0X4c or 4c 1 or 3 or 4 or 7 01001101 0X4d or 4d 2 or 3 or...

Page 63: ... 0X7b or 7b 3 or 4 or 5 or 6 or 7 01111100 0X7c or 7c 1 or 3 or 4 or 5 or 6 or 7 01111101 0X7d or 7d 2 or 3 or 4 or 5 or 6 or 7 01111110 0X7e or 7e 1 or 2 or 3 or 4 or 5 or 6 or 7 01111111 0X7f or 7f 8 10000000 0X80 or 80 1 or 8 10000001 0X81 or 81 2 or 8 10000010 0X82 or 82 1 or 2 or 8 10000011 0X83 or 83 3 or 8 10000100 0X84 or 84 1 or 3 or 8 10000101 0X85 or 85 2 or 3 or 8 10000110 0X86 or 86 1...

Page 64: ...or b8 1 or 4 or 5 or 6 or 8 10111001 0Xb9 or b9 2 or 4 or 5 or 6 or 8 10111010 0Xba or ba 1 or 2 or 4 or 5 or 6 or 8 10111011 0Xbb or bb 3 or 4 or 5 or 6 or 8 10111100 0Xbc or bc 1 or 3 or 4 or 5 or 6 or 8 10111101 0Xbd or bd 2 or 3 or 4 or 5 or 6 or 8 10111110 0Xbe or be 1 or 2 or 3 or 4 or 5 or 6 or 8 10111111 0Xbf or bf 7 or 8 11000000 0Xc0 or c0 1 or 7 or 8 11000001 0Xc1 or c1 2 or 7 or 8 1100...

Page 65: ...or 6 or 7 or 8 11110001 0Xf1 or f1 2 or 5 or 6 or 7 or 8 11110010 0Xf2 or f2 1 or 2 or 5 or 6 or 7 or 8 11110011 0Xf3 or f3 3 or 5 or 6 or 7 or 8 11110100 0Xf4 or f4 1 or 3 or 5 or 6 or 7 or 8 11110101 0Xf5 or f5 2 or 3 or 5 or 6 or 7 or 8 11110110 0Xf6 or f6 1 or 2 or 3 or 5 or 6 or 7 or 8 11110111 0Xf7 or f7 4 or 5 or 6 or 7 or 8 11111000 0Xf8 or f8 1 or 4 or 5 or 6 or 7 or 8 11111001 0Xf9 or f9...

Page 66: ...1f or 1f 6 00100000 0X20 or 20 1 or 6 00100001 0X21 or 21 2 or 6 00100010 0X22 or 22 1 or 2 or 6 00100011 0X23 or 23 3 or 6 00100100 0X24 or 24 1 or 3 or 6 00100101 0X25 or 25 2 or 3 or 6 00100110 0X26 or 26 1 or 2 or 3 or 6 00100111 0X27 or 27 4 or 6 00101000 0X28 or 28 1 or 4 or 6 00101001 0X29 or 29 2 or 4 or 6 00101010 0X2a or 2a 1 or 2 or 4 or 6 00101011 0X2b or 2b 3 or 4 or 6 00101100 0X2c o...

Page 67: ... or 4 or 5 or 7 01011011 0X5b or 5b 3 or 4 or 5 or 7 01011100 0X5c or 5c 1 or 3 or 4 or 5 or 7 01011101 0X5d or 5d 2 or 3 or 4 or 5 or 7 01011110 0X5e or 5e 1 or 2 or 3 or 4 or 5 or 7 01011111 0X5f or 5f 6 or 7 01100000 0X60 or 60 1 or 6 or 7 01100001 0X61 or 61 2 or 6 or 7 01100010 0X62 or 62 1 or 2 or 6 or 7 01100011 0X63 or 63 3 or 6 or 7 01100100 0X64 or 64 1 or 3 or 6 or 7 01100101 0X65 or 65...

Page 68: ... 5 or 8 10010101 0X95 or 95 2 or 3 or 5 or 8 10010110 0X96 or 96 1 or 2 or 3 or 5 or 8 10010111 0X97 or 97 4 or 5 or 8 10011000 0X98 or 98 1 or 4 or 5 or 8 10011001 0X99 or 99 2 or 4 or 5 or 8 10011010 0X9a or 9a 1 or 2 or 4 or 5 or 8 10011011 0X9b or 9b 3 or 4 or 5 or 8 10011100 0X9c or 9c 1 or 3 or 4 or 5 or 8 10011101 0X9d or 9d 2 or 3 or 4 or 5 or 8 10011110 0X9e or 9e 1 or 2 or 3 or 4 or 5 or...

Page 69: ... 11010000 0Xd0 or d0 1 or 5 or 7 or 8 11010001 0Xd1 or d1 2 or 5 or 7 or 8 11010010 0Xd2 or d2 1 or 2 or 5 or 7 or 8 11010011 0Xd3 or d3 3 or 5 or 7 or 8 11010100 0Xd4 or d4 1 or 3 or 5 or 7 or 8 11010101 0Xd5 or d5 2 or 3 or 5 or 7 or 8 11010110 0Xd6 or d6 1 or 2 or 3 or 5 or 7 or 8 11010111 0Xd7 or d7 4 or 5 or 7 or 8 11011000 0Xd8 or d8 1 or 4 or 5 or 7 or 8 11011001 0Xd9 or d9 2 or 4 or 5 or 7...

Page 70: ...tatus relay output Activate relay output when Corresponding 8 bits binary numbers Mask value N A 00000000 0X0 or 0 Power fail on Power 1 00000001 0X1 or 1 Power fail on Power 2 00000010 0X2 or 2 Power fail on Power 1 or Power 2 00000011 0X3 or 3 Switch is selected as master switch 00000100 0X4 or 4 Power fail on Power 1 or switch is selected as master switch 00000101 0X5 or 5 Power fail on Power 2...

Page 71: ... 20 00100000 6 21 00100001 1 or 6 22 00100010 2 or 6 23 00100011 1 or 2 or 6 24 00100100 3 or 6 25 00100101 1 or 3 or 6 26 00100110 2 or 3 or 6 27 00100111 1 or 2 or 3 or 6 28 00101000 4 or 6 29 00101001 1 or 4 or 6 2a 00101010 2 or 4 or 6 2b 00101011 1 or 2 or 4 or 6 2c 00101100 3 or 4 or 6 2d 00101101 1 or 3 or 4 or 6 2e 00101110 2 or 3 or 4 or 6 2f 00101111 1 or 2 or 3 or 4 or 6 30 00110000 5 o...

Page 72: ...r 7 5c 01011100 3 or 4 or 5 or 7 5d 01011101 1 or 3 or 4 or 5 or 7 5e 01011110 2 or 3 or 4 or 5 or 7 5f 01011111 1 or 2 or 3 or 4 or 5 or 7 60 01100000 6 or 7 61 01100001 1 or 6 or 7 62 01100010 2 or 6 or 7 63 01100011 1 or 2 or 6 or 7 64 01100100 3 or 6 or 7 65 01100101 1 or 3 or 6 or 7 66 01100110 2 or 3 or 6 or 7 67 01100111 1 or 2 or 3 or 6 or 7 68 01101000 4 or 6 or 7 69 01101001 1 or 4 or 6 ...

Page 73: ... or 8 96 10010110 2 or 3 or 5 or 8 97 10010111 1 or 2 or 3 or 5 or 8 98 10011000 4 or 5 or 8 99 10011001 1 or 4 or 5 or 8 9a 10011010 2 or 4 or 5 or 8 9b 10011011 1 or 2 or 4 or 5 or 8 9c 10011100 3 or 4 or 5 or 8 9d 10011101 1 or 3 or 4 or 5 or 8 9e 10011110 2 or 3 or 4 or 5 or 8 9f 10011111 1 or 2 or 3 or 4 or 5 or 8 a0 10100000 6 or 8 a1 10100001 1 or 6 or 8 a2 10100010 2 or 6 or 8 a3 10100011 ...

Page 74: ... d1 11010001 1 or 5 or 7 or 8 d2 11010010 2 or 5 or 7 or 8 d3 11010011 1 or 2 or 5 or 7 or 8 d4 11010100 3 or 5 or 7 or 8 d5 11010101 1 or 3 or 5 or 7 or 8 d6 11010110 2 or 3 or 5 or 7 or 8 d7 11010111 1 or 2 or 3 or 5 or 7 or 8 d8 11011000 4 or 5 or 7 or 8 d9 11011001 1 or 4 or 5 or 7 or 8 da 11011010 2 or 4 or 5 or 7 or 8 db 11011011 1 or 2 or 4 or 5 or 7 or 8 dc 11011100 3 or 4 or 5 or 7 or 8 d...

Page 75: ...6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 8 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 1 on 1 on 1 on 1 on 1 on 1 on 1 on 1 on 0 off 0 off 0 off 0 off 0 off 0 off 0 off 0 off Table 9 Clarify current link status by returned cvalue Returned cvalue in hexadecimal format Corresponding 8 bits binary numbers Indicating there is link loss occurring on port s 0 00000000 N A 1 00000001 1 2 00000010 ...

Page 76: ...5 or 6 35 00110101 1 or 3 or 5 or 6 36 00110110 2 or 3 or 5 or 6 37 00110111 1 or 2 or 3 or 5 or 6 38 00111000 4 or 5 or 6 39 00111001 1 or 4 or 5 or 6 3a 00111010 2 or 4 or 5 or 6 3b 00111011 1 or 2 or 4 or 5 or 6 3c 00111100 3 or 4 or 5 or 6 3d 00111101 1 or 3 or 4 or 5 or 6 3e 00111110 2 or 3 or 4 or 5 or 6 3f 00111111 1 or 2 or 3 or 4 or 5 or 6 40 01000000 7 41 01000001 1 or 7 42 01000010 2 or...

Page 77: ...f 01101111 1 or 2 or 3 or 4 or 6 or 7 70 01110000 5 or 6 or 7 71 01110001 1 or 5 or 6 or 7 72 01110010 2or 5 or 6 or 7 73 01110010 1 or 2or 5 or 6 or 7 74 01110100 3 or 5 or 6 or 7 75 01110101 1 or 3 or 5 or 6 or 7 76 01110110 2 or 3 or 5 or 6 or 7 77 01110111 1 or 2 or 3 or 5 or 6 or 7 78 01111000 4 or 5 or 6 or 7 79 01111001 1 or 4 or 5 or 6 or 7 7a 01111010 2 or 4 or 5 or 6 or 7 7b 01111011 1 o...

Page 78: ...r 8 ac 10101100 3 or 4 or 6 or 8 ad 10101101 1 or 3 or 4 or 6 or 8 ae 10101110 2 or 3 or 4 or 6 or 8 af 10101111 1 or 2 or 3 or 4 or 6 or 8 b0 10110000 5 or 6 or 8 b1 10110001 1 or 5 or 6 or 8 b2 10110010 2 or 5 or 6 or 8 b3 10110011 1 or 2 or 5 or 6 or 8 b4 10110100 3 or 5 or 6 or 8 b5 10110101 1 or 3 or 5 or 6 or 8 b6 10110110 2 or 3 or 5 or 6 or 8 b7 10110111 1 or 2 or 3 or 5 or 6 or 8 b8 10111...

Page 79: ...0100 3 or 6 or 7 or 8 e5 11100101 1 or 3 or 6 or 7 or 8 e6 11100110 2 or 3 or 6 or 7 or 8 e7 11100111 1 or 2 or 3 or 6 or 7 or 8 e8 11101000 4 or 6 or 7 or 8 e9 11101001 1 or 4 or 6 or 7 or 8 ea 11101010 2 or 4 or 6 or 7 or 8 eb 11101011 1 or 2 or 4 or 6 or 7 or 8 ec 11101100 3 or 4 or 6 or 7 or 8 ed 11101101 1 or 3 or 4 or 6 or 7 or 8 ee 11101110 2 or 3 or 4 or 6 or 7 or 8 ef 11101111 1 or 2 or 3...

Page 80: ...tput is activated bit 3 will be set as 1 Table 11 Displayed hexadecimal number and current system status conditions Returned svalue in hexadecimal format Corresponding 8 bits binary numbers Showing current system status condition s 0 00000000 a 1 00000001 b 2 00000010 c 3 00000011 a or b 4 00000100 c 5 00000101 a or c 6 00000110 b or c 7 00000111 a or b or c 8 00001000 d 9 00001001 a or d 0A 00001...

Page 81: ... 1 Enable Ring Pair 1 Table 14 DIPSW values and corresponding Jumpers states Jumpers on ON state Corresponding 8 bits binary numbers DIPSW value in hexadecimal format N A 00000000 0 Jumper 6 00000001 1 Jumper 5 00000010 2 Jumper 5 6 00000011 3 Jumper 4 00000100 4 Jumper 4 6 00000101 5 Jumper 4 5 00000110 6 Jumper 4 5 6 00000111 7 Jumper 3 00001000 8 Jumper 3 6 00001001 9 Jumper 3 5 00001010 A Jump...

Page 82: ... ms 800 ms Forwarding Delay 30s 28s 26s 24s 22s 20s 18s 16s Hello Time 10s 10s 10s 10s 10s 10s 10s 10s Max Age 40s 40s 40s 40s 40s 38s 34s 30s Roteray SW position 7 6 5 4 3 2 1 0 Recovery Time 700 ms 600 ms 500 ms 400 ms 300 ms 200 ms 100 ms N A Forwarding Delay 14s 12s 10s 8s 6s 4s 4s N A Hello Time 10s 10s 8s 6s 4s 2s 1s N A Max Age 26s 22s 18s 14s 10s 6s 6s N A ss TDRS4050601 ...