5.2.
Thermocouple Calibration
Type Code
The following table shows all of the type code for use in thermocouple.
Type Code
14
18
0E
10
12
13
15
16
19
0F
11
17
Thermocouple
Calibration Range
00
01
02
Zero Input
0 mV
0 mV
0 mV
Span Input
+15 mV
+50 mV
+100 mV
The calibration procedure is similar to the section 5.1. But, the difference between them is
that the ET-7X00/PET-7X00 doesn’t directly support type code - 0E ~ 19 for AI calibration,
so you need to change the channel 0 as range - 00 ~ 02 to complete the work (refer to
section 5.1 step 3).
Step 1 Warm up the module for latest 30 minutes.
Step 2 Set the type code to the type you wish to calibrate.
Step 3 Enable calibration.
Step 4 Apply the zero calibration voltage to channel 0.
Step 5 Send the zero calibration command.
Step 6 Apply the span calibration voltage to channel 0.
Step 7 Send the span calibration command.
Step 8 Disable calibration.
For example
If you want to calibrate type 0E, you need to set the channel 0 as range - 01.