background image

 

 

5

 

2.2.2 Downflow Installation 

 
 
When the furnace is installed in the downflow position on a 
combustible floor, the clearances from combustibles must 
be adhered to. The downflow base DFB-103 or 
KLASB0901DET can be used to ensure these clearances. 
Refer to Figure 3 and the installation instructions provided 
with the base. 

 

The burner must always be installed in the same manner, 
regardless of the discharge position of the furnace. Refer 
to Figure 3 for additional details. 
 

 

Figure 3 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

2.2.3 Horizontal Installation 

 

When the furnace is installed in the horizontal position, 
either suspended or on a combustible floor with a choice of 
right or left discharge, the clearances from combustible 
material must be adhered to. If the unit is installed on a 
combustible floor, the horizontal floor base HFB-101 or 
KLASB0701DET can be used to ensure these clearances. 
Refer to the instructions supplied with the base. 

 

The burner must always be installed in the same manner, 
regardless of the discharge position of the furnace. Refer 
to Figure 4 for additional details. 

Figure 4

 

 
 

 
 
 
 

2.3 ELECTRICAL

 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted 
ground to minimize the risk of bodily harm, if ever an 
electrical problem develops. A green ground screw is 
supplied with the control box for that purpose.

  

 

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local 
codes. 

 

The control system depends on the correct polarity of 
the power supply. Connect “HOT” wire (H) and 
“NEUTRAL” wire (N) as shown in Figures 6 and 7, p. 18 
and 19. 

 

A separate line voltage supply should be used, with 
fused disconnect switch or circuit breaker, between the 
main power panel and the unit. 

 

Only copper wire may be used for the 115V circuit on 
this unit. If wires need to be changed, the replacements 
must have the same temperature resistance as the 
originals. 

2.4 INSTALLATION

 

OF

 

THE

 

THERMOSTAT 

A thermostat must be installed to control the 
temperature of the area to be heated. Follow the 
instructions supplied with the thermostat. Also refer to 
the wiring diagrams provided with the heating/air 
conditioning unit. The connections must be made as 
indicated on the following diagrams and the wiring 
diagrams, p. 18 and 19. 

 

Thermostat Wiring 

Heating and Air Conditioning 

with 4-speed motor

 

 
 
 
 
 
 
 
 
 

 

Filter 20 x 24 

Downflow base is 
required for 
combustible floor 

Burner position 

DNS-1227A 

Horizontal floor base required 
for combustible floor 

Burner position 

Filter 20 x 24 

DNS-1227A 

445 01 4101 00

Summary of Contents for OMF112K14A

Page 1: ...HE INFORMATION IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFER...

Page 2: ...LE SPEED MOTORS 9 2 13 INSTALLATION OF ACCESSORIES 9 3 OPERATION 10 3 1 START UP 10 3 2 OPERATING SEQUENCE OIL HEATING MODE 10 3 3 CHECKS AND ADJUSTMENTS 10 4 MAINTENANCE 12 4 1 CLEANING THE HEAT EXCH...

Page 3: ...on such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform to loca...

Page 4: ...t designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to p...

Page 5: ...f bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance with the current ANSI NFPA 70...

Page 6: ...e burner for the first time adjust the air and turbulator settings to those listed in this manual Once the burner becomes operational final adjustments will be required Refer to section 3 of this manu...

Page 7: ...Test The purpose of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outle...

Page 8: ...istance 2 10 DUCTING WARNING Poisonous carbon monoxide gas hazard DO NOT draw return air from inside a closet or utility room Return air MUST be sealed to the furnace casing Failure to properly seal d...

Page 9: ...GPH OFF OFF A 0 68 ON OFF B 0 80 OFF ON C ALL ON ON D ALL 2 13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard Turn OFF electrical power at the fuse box or service panel before making any...

Page 10: ...are appropriate and according to the specifications in this manual 8 The blower start stop delays are satisfactory 9 The thermostat of the room is in the heating mode and is set higher than the ambie...

Page 11: ...bove the burner is a measurement necessary to determine if there is a blockage in the heat exchanger or the flue pipe Refer to the Technical Specifications in this manual for overfire pressure values...

Page 12: ...combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the burner for proper...

Page 13: ...ephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient te...

Page 14: ...n 85 2 85 0 85 2 85 0 RIELLO BURNER MODEL 40 BF5 Direct vent DV Burner tube insertion length inches Nozzle Delavan 0 60 70A 0 70 70A 0 60 70A 0 70 70A Minimum and Maximum pump pressure PSIG 130 to 160...

Page 15: ...me ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON All 13 45 sec 100 0 sec 100 2 m...

Page 16: ...ACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN 6 ft OF...

Page 17: ...17 Figure 5 Furnace dimensions 445 01 4101 00...

Page 18: ...18 Figure 6 Wiring Diagram 4 Speed Motor PSC 445 01 4101 00...

Page 19: ...19 Figure 7 Wiring Diagram Variable Speed Motor ECM 445 01 4101 00...

Page 20: ...20 PARTS LIST With 4 Speed motor PSC B50091B 445 01 4101 00...

Page 21: ...MBLY Blower motor and capacitor included 24 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 25 B03118 01 ELECTRICAL KIT BVSO EXT 26 L07F003 ROCKER SWITCH DPST 27 L04I013 STRAIN RELIEF BUSHING 28 L04J001 CABLE...

Page 22: ...22 PARTS LIST With variable speed motor ECM B50092B 445 01 4101 00...

Page 23: ...EMBLY Blower motor and capacitor included 24 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 25 B03118 01 ELECTRICAL KIT BVSO EXT 26 L04I013 STRAIN RELIEF BUSHING 27 L04J001 CABLE CLAMP 9 16 WHITE 28 B03640 WI...

Reviews: