background image

 

iDRY Series Heatless Regenerated Dryers: IOM10003-C 

(Rev. A)

 

   

13

 

 
5.2 

Start-up Procedures 

 

 

 

During the first start-up or start-up after a long period of inactivity or following maintenance, the technician 
must comply with the instructions below.  The start-up must be performed by qualified personnel only.

 

 

 

 

 

 

The employee that operates the machine must wear hearing and eye protection before operating the dryer.  
Each employee must select a proper personal protection device (PPD) hearing protector such as earmuffs, 
ear canal caps or earplugs in order to prevent permanent hearing damage or loss. 

 

Start-up Sequence 

 

Please read and understand the entire manual before operating the dryer  

 

Verify the factory settings 

 

Verify the wiring diagrams that pertain to your unit and ensure the correct power supply is connected 

Do not energize the circuit at this time

 

 

Verify that proper short circuit protection has been provided following all applicable codes and regulations 

 

Verify that all the steps of in the previous chapters relating to installation have been observed 

 

Verify that the connection to the compressed air system is correct 

 

Verify that the condensate drain pipe is properly fastened and connected to a collection system or container 

 

Remove any packaging and other material that might obstruct the area around the dryer 

 
Before starting the dryer your compressor should be running, your compressed air system pressurized and the dryer 
bypassed and not yet pressurized. 
 

 

 

1.

 

With the dryer bypassed and in isolation (see page 14) 

2.

 

SLOWLY 

open the inlet isolation valve allowing compressed air into the dryer.  It is critical that the dryer 

be pressurized slowly to prevent fluidization of the desiccant bed.  Keep the outlet isolation valve closed 
at this time. 

3.

 

SLOWLY 

open the outlet isolation valve.  All valves are now in their open positions and compressed air is 

flowing through both towers and downstream.

 

4.

 

Close the dryer bypass valve.  The bypass valve must be bubble tight to prevent any moisture from 
contaminating the dry air outlet from the dryer. 

5.

 

Plug in the dryer and energize the electrical circuit – the dryer is now ON. 

6.

 

Verify that the controller is on. 

7.

 

Check all piping for compressed air leaks. 

8.

 

Test the condensate drain on the pre-filter. 

9.

 

After 1-minutes from start-up the adsorption tower B will be depressurized. 

10.

 

Wait for the dryer to make 10 full cycles (i.e. the depressurization from tower A to tower B). 

11.

 

The dryer will make the first 5 cycles short cycles, running at 50% run time without regard for dew point. 

12.

 

The pressure swing cycles occurs, every 5 minutes (outlet dew point of -40°F). 

 

 
NOTE: During the first days in operation, the dew point cannot be guaranteed because the adsorption material can 
contain humidity from storage.  At the first start-up or start-up after a long inactivity period or following maintenance 
shutdowns, we recommend operating the dryer at a reduced nominal flow of 50% during the first two days. 
 
 
 
 
 
 
 
 
 

Summary of Contents for iDRY

Page 1: ...his manual contains important information and should be made available to all personnel who operate and or maintain this product Carefully read this manual before attempting to operate or perform main...

Page 2: ......

Page 3: ...ERAL FUNCTION 7 3 1 Technical Data by Model Size 7 3 2 Correction Factors 8 3 3 General Function 8 3 4 Flow Diagram 9 3 5 Cycle Operation 10 4 PURGE VALVE ADJUSTMENT 11 5 START UP 12 5 1 Verification...

Page 4: ...nt 21 8 5 Inlet and Exhaust Valve Repair 21 9 TROUBLESHOOTING GUIDE 22 10 MAINTENANCE AND SPARE PARTS 25 10 1 Required Maintenance Parts 25 10 2 Spare Parts 27 11 DISMANTLING OF THE DRYER 28 12 ELECTR...

Page 5: ...and or operate the dryer In most countries states cities and or local municipalities the installation may only be carried out by a licensed installation company Inspections must be carried out by a q...

Page 6: ...n of certain installation conditions in particular Voltage and frequency of the electrical power supplied Pressure temperature flow rate and chemical composition of the incoming compressed air Ambient...

Page 7: ...to the dryer In addition we recommend the use of a iMAT zero air loss drain on the pre filter and at all other condensate collection points especially those upstream of the dryer Locate the coalescin...

Page 8: ...istent dryer inlet flow provided by an upstream receiver while providing the most reliable shop air supply due to the downstream receiver Under no circumstances should the peak demand air flow exceed...

Page 9: ...230 230 340 340 480 625 795 940 Outlet Pressure Dew Point F 40 Minimum Ambient Temperature F 40 Maximum Ambient Temperature F 120 Standard Inlet Air Temperature F 100 Maximum Inlet Air Temperature F 1...

Page 10: ...used for the regeneration process and expelled along with the condensate through the silencers The saturated inlet air is cycled through each of the two desiccant beds in an alternating sequence where...

Page 11: ...ficiency iPUR filters 0 01 micron filtration grade coalescing pre filter with differential pressure gauge and either a float drain or iMAT 1 0 micron filtration grade particulate post filter different...

Page 12: ...terial dragging away the humidity through the PV B valve 2 and exits the silencers 3 At the end of this stage the adsorption material of vessel B is completely regenerated Step 3 The purge exhaust val...

Page 13: ...below is based on the number of turns from the closed position 1 Loosen the screw using a flathead screwdriver or allen head 2 Turn the purge flow control valve clockwise until the stopping point the...

Page 14: ...ts indicated on the data plate Installation precautions must be taken in order to limit the vibration that can occur during the operation of the dryer Therefore we recommend using flexible connecting...

Page 15: ...running your compressed air system pressurized and the dryer bypassed and not yet pressurized 1 With the dryer bypassed and in isolation see page 14 2 SLOWLY open the inlet isolation valve allowing c...

Page 16: ...ressurized suddenly This will cause degradation and dusting of the desiccant bed The dryer is designed for a maximum operating pressure of 150 psig as standard 6 ISOLATION AND SHUT DOWN PROCEDURES Use...

Page 17: ...alve PV and IV The controller has two additional LEDs used to indicate power and service in the upper left corner of the display as shown by the corresponding icons During normal operation the power L...

Page 18: ...ll Nema cycles as though the operating voltage has been interrupted i e as after RESET 7 4 Controller Outputs The controller outputs information two ways one to the controller display the other to the...

Page 19: ...e is the time selected for step 3 in Section 3 5 The two DIP switches can be adjusted to four 4 regeneration times between 60 and 120 seconds in 20 second increments as follows 00 60 seconds factory s...

Page 20: ...l flash red indicating that service is overdue 7 7 Power Requirements The controller operates on 100 120VAC 50 60Hz The units are shipped with an installed standard US 120 volt cord for convenience Be...

Page 21: ...kes place correctly at the set cycle times Check that the tower pressure gauge of the regenerating tower reads 0 psig while the drying tower reads full line pressure ANNUALLY Replace the pre and post...

Page 22: ...cement and maintenance such as the filter elements exhaust silencers and desiccant material NOTE The maintenance alarms reminders do not change the operation of the controller in any way 8 3 Fuses One...

Page 23: ...ettling may be required in order to fit the specified fill amount into the tower Tank sizes may be the same for multiple models so do not be concerned if the tower is not entirely full 6 Desiccant tha...

Page 24: ...lectric Check the operation of inlet and purge exhaust valves Ensure Control pilot air is delivering at 80 psi Ensure DIN connectors are properly attached to solenoid valves See controller troubleshoo...

Page 25: ...exhaust troubleshooting Back pressure Purge muffler fouled Vessel screen Restricted purge piping Bad Purge Exhaust Valve Replace with new Empty towers remove screens and clean Clean See purge Exhaust...

Page 26: ...ing Dirty element Electrical Differential pressure gauge Ensure proper dryer sequence Contaminated filter replace element Faulty electrical signal Clean check and or replace Controller Defective No po...

Page 27: ...E 12S 00 iELE 15S iELE 15S 00 iELE 18S iELE 18S 00 iELE 20S iELE 20S 00 iELE 25S iELE 25S 00 Post filter Element 1 0 m iELE 07F iELE 07F 00 iELE 10F iELE 10F 00 iELE 12F iELE 12F 00 iELE 15F iELE 15F...

Page 28: ...802 4026888 1 Exhaust Valve Actuator 4026416 4026889 1 Exhaust Valve Actuator 4020804 4026890 2 Exhaust Valve Actuator 4020806 4026891 Service Seal Kit Service Seal Kit 4027898 1 Service Seal Kit 4027...

Page 29: ...rol Valve 1 4020765 1 Purge Flow Control Valve 4020766 Electronic Controller MINI Electronic Controller PLC 4026540 Solenoid Valve Assembly Complete MAC Solenoid Valve Assembly 4024046 Tower Pressure...

Page 30: ...g Aluminum Epoxy paint Filter cartridge Filtering material PVC Oil Solenoid valve Bronze Steel Techno polymer PVC Condensate Drain PVC Aluminum Steel Bronze Silencers Aluminum Stainless steel Safety V...

Page 31: ...of process air through the dryer Safety Relief Valves Valves on each tower to protect the vessels from overpressure situations The setting is indicated on each valve Purge Exhaust Silencer Installed t...

Page 32: ......

Page 33: ...ated Dryers IOM10003 C Rev A Independent Compressor Partners LLC P O Box 206 Jeffersonville IN 47131 www i compressorpartners com Subject to technical changes without prior notice errors not excluded...

Reviews: