ICP DAS, ZT-2005-C8 User Manual, Version v1.0.1 Page 20
Copyright © 2014 by ICP DAS Co., Ltd. All Rights Reserved.
5.2.2
Overview of the DCON Command Set
General Command Set
Command
Response
Description
Section
%AANNTTCCFF !AA
Sets the Configuration of the Module
5.2.3
#AA
>(Data)
Reads the Analog Input Data from all
Channels
5.2.4
#AAN
>(Data)
Reads the Analog Input Data from a
Specific Channel
5.2.5
$AA0Ci
!AA
Performs an Analog Input Zero Calibration
of a Specific Channel on the Module
5.2.6
$AA1Ci
!AA
Performs an Analog Input Span Calibration
of a Specific Channel on the Module
5.2.7
$AA0
!AA
Performs an Analog Input Span Calibration
on the Module
5.2.8
$AA1
!AA
Performs an Analog Input Zero Calibration
on the Module
5.2.9
$AA2
!AATTCCFF
Reads the Configuration of the Module
5.2.10
$AA5VV
!AA
Enables or Disables Specific Analog Input
Channels
5.2.11
$AA6
!AAVV
Reads whether each Analog Input Channel
is Enabled or Disabled
5.2.12
$AAF
!AA(Data)
Reads the Firmware Version of the Module
5.2.13
$AAM
!AA(Data)
Reads the Name of the Module
5.2.14
$AAP
!AASC
Reads the communication protocol
5.2.15
$AAS1
!AA
Reloads the Default Calibration Parameters
5.2.16
~AAD
!AAT
Reads the temperature scaling
5.2.17
~AADT
!AA
Sets the temperature scaling to either °C
or °F
5.2.18
~AAEV
!AA
Enables/Disables calibration
5.2.19
~AARE
!AAsc
Read RF Encryption Setting
5.2.20
@AAA2CiToo
!AA
Sets the temperature offset of a
channel
5.2.21
@AAA3Ci
!AA
Reads the temperature offset of
a channel
5.2.22