RTD Type Setting table
:
Open RTD
:
SW2-6 determines output range of SG-3013 when RTD wiring open.
Current Output
:
SW2-7 determines current output range.
Voltage Output
:
SW2-8 determines Voltage output range.
No Switch Temperature Range (
℃
)
RTD Type
1 0x00 00000
-200~200
Platinum 100,
α
= 0.00385
2 0x01 10000
-200~600
3 0x02 01000
-100~100
4 0x03 11000
-100~0
5 0x04 00100
-100~200
6 0x05 10100
-50~50
7 0x06 01100
-50~150
8 0x07 11100
0~100
9 0x08 00010
0~200
10 0x09 10010
0~600
11 0X0A 01010
-200~200
Platinum 100,
α
= 0.003916
12 0X0B 11010
-200~600
13 0X0C 00110
-100~100
14 0X0D 10110
-100~0
15 0X0E 01110
-100~200
16 0X0F 11110
-50~50
17 0x10 00001
-50~150
18 0x11 10001
0~100
19 0x12 01001
0~200
20 0x13 11001
0~600
21
0x14
00101
-200 ~ 600
Platinum 1000,
α
= 0.00385
22
0x15
10101
-80 ~ 100
Nickel 120
23
0x16
01101
0 ~ 100
24 0x17 11101
0~300
25 0x18 00011
-80~300
26
0x19
10011
-20 ~ 150
Cu 100 at 0
℃
,
α
=0.00421
27
0x1A
01011
0 ~ 200
Cu 100 at 25
℃
,
α
=0.00427
28
0X1B
11011
-20 ~ 150
Cu 1000 at 0
℃
,
α