background image

ICP DAS Co., LTD 

PM-4324 Series Quick Start V1.3 

Page 7 

Communication 

2.6. 

RS-485 & CAN setting 

  Default setting for RS-485: 

19200, n, 8, 1

 ,

for CAN:

 125K bps

 

  DIP switch (SW1-SW6) is used for Modbus address(or CANopen Node ID) 

setting, default is 1, i.e. all OFF 

For example:

 Modbus address(or CANopen Node ID) is 10

find the table of 

DIP switch 1-6 is 

ON, OFF, OFF, ON, OFF, OFF 

  SW1

SW6 setting 

Setting Modbus-RTU address/ CANopen Node ID for communication (1-64) 

Modbus Address 

SW 1 

  SW 2 

SW 3 

SW 4 

SW 5 

SW 6 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

OFF 

OFF 

ON

 

ON

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

OFF 

ON

 

OFF 

ON

 

OFF 

OFF 

OFF 

OFF 

ON

 

ON

 

OFF 

OFF 

OFF 

ON

 

ON

 

ON

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

10 

ON

 

OFF 

OFF 

ON

 

OFF 

OFF 

 

  SW7

SW8 setting 

PM-4324

For Baud Rate Setting

 

RS-485 

CAN 

  SW 7 

SW8 

9600 bps 

125k (Default) 

 

OFF 

OFF 

19200 

 

 

250k bps 

ON 

OFF 

38400 bps 

500k bps 

OFF 

ON

 

115200 bps 

1M bps 

ON 

ON

 

 

PM-4324

Select the different wiring mode   

(Please select the Software setting, if 1P2W-1CT or 1P3W-2CT is used) 

Models 

PM-4324/PM-4324-CPS/PM-4324-MTCP

 

Wiring 

SW 9 

SW 10 

Software setting 

OFF 

OFF 

3P3W-2CT 

ON

 

OFF 

3P3W-3CT 

OFF 

ON

 

3P4W-3CT 

ON

 

ON

 

 

2.7. 

Add the Bias Resistor on RS-485 Network for stable signal 

The RS-485 master is required to provide the bias for PM-4324 series. 

Summary of Contents for PM-4324 Series

Page 1: ...any damage resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and relia...

Page 2: ...ly the ex factory attached CT s can be used The other CT s for example from panel will damage the instrument due to its large current around 5A 3 When more than one smart meter PM 4324 series are inst...

Page 3: ...sign on CT s follows current flow direction K L Note it must be in the same direction Connect the voltage input terminal N C B A for PM 4324 in the three phase order as follows on N C B A Attention p...

Page 4: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 4 2 5 Wiring 1P2W 1CT PM 4324 1P3W 2CT PM 4324...

Page 5: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 5 3P3W 2CT PM 4324 3P3W 3CT PM 4324 DIP switch Wiring mode SW 9 SW 10 3P3W 3CT OFF ON...

Page 6: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 6 3P4W 3CT PM 4324 DIP switch Wiring mode SW 9 SW 10 3P4W 3CT ON ON...

Page 7: ...3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF OFF 9 OFF OFF OFF ON OFF OFF 10 ON OFF OFF ON OFF OFF SW7...

Page 8: ...8 Otherwise the tM SG4 or SG 785 should be added to provide the bias All ICP DAS controllers and converters provide the bias 2 8 Ethernet setting Ethernet default settings IP Address 192 168 255 1 Su...

Reviews: