ICP DAS Co., LTD 

PM-4324 Series Quick Start V1.3 

Page 3 

2.3. 

Connection 

  PM-4324 Series 

 

Please  firstly check the current input 
terminal, and then in white black, white black, 
white black wire sequences (CT1-K, CT1-L, 
CT2-K,  CT2-L,  CT3-K,  CT3-L). Then 
connect the CT’s, and close the CT clip. 
Make sure the arrow direction sign on CT’s 

follows current flow direction

K→L

 

Note: it must be in the

 

same direction

.   

Connect the voltage input terminal N C B A. for PM-4324, in the three phase 
order as follows on N C B A.   

Attention please!!    For 3P3W-2CT, connect in N C A phase sequence, 
do not connect phase B (Check the diagram). 

 

2.4. 

CT’s installation steps 

 

  At the bottom of the CT, 

there is a “K

→L” mark. 

 

 

  Open the CT clip. 

 

  Make sure the power current 

direction follow the “K

→L” 

mark on the CT and then 
close the CT clip. 

 

  Installation steps finished. 

Summary of Contents for PM-4324 Series

Page 1: ...any damage resulting from the use of this product ICP DAS reserves the right to change this manual at any time without notice The information furnished by ICP DAS is believed to be accurate and relia...

Page 2: ...ly the ex factory attached CT s can be used The other CT s for example from panel will damage the instrument due to its large current around 5A 3 When more than one smart meter PM 4324 series are inst...

Page 3: ...sign on CT s follows current flow direction K L Note it must be in the same direction Connect the voltage input terminal N C B A for PM 4324 in the three phase order as follows on N C B A Attention p...

Page 4: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 4 2 5 Wiring 1P2W 1CT PM 4324 1P3W 2CT PM 4324...

Page 5: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 5 3P3W 2CT PM 4324 3P3W 3CT PM 4324 DIP switch Wiring mode SW 9 SW 10 3P3W 3CT OFF ON...

Page 6: ...ICP DAS Co LTD PM 4324 Series Quick Start V1 3 Page 6 3P4W 3CT PM 4324 DIP switch Wiring mode SW 9 SW 10 3P4W 3CT ON ON...

Page 7: ...3 OFF ON OFF OFF OFF OFF 4 ON ON OFF OFF OFF OFF 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 ON ON ON OFF OFF OFF 9 OFF OFF OFF ON OFF OFF 10 ON OFF OFF ON OFF OFF SW7...

Page 8: ...8 Otherwise the tM SG4 or SG 785 should be added to provide the bias All ICP DAS controllers and converters provide the bias 2 8 Ethernet setting Ethernet default settings IP Address 192 168 255 1 Su...