
M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
36
2.7 #AAN
Description:
Reads the digital input counter of channel N.
Syntax:
#AAN [CHKSUM](CR)
#
Delimiter character
AA
Address of the module to be set (00 to FF)
N
The channel to be read (0 to F)
Response:
Valid Command:
!(Data)[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command.
?
Delimiter for an invalid command.
An invalid command is returned if the
specified channel is incorrect.
(Data)
Five decimal digits representing the digital
input counter data of the specified channel
(00000 to 65535).
AA
Address of the responding module (00 to FF)