M-7065 User’s Manual
Ver2.0, Dec. /200
8
---
124
3.8.4 06(0x06) Set Communication
This sub-function code is used to set the
communication protocol of a module.
Request
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x06
03
Reserved
1 Byte
0x00
04
Baud Rate
1 Byte
0x0A
05
Reserved
1 Byte
0x00
06
Parity
1 Byte
0 : N81
1 : N82
2 : E81
3 : O81
07
Reserved
1 Byte
0x00
08
Protocol Mode
1 Byte
0 : DCON
1 : Modbus RTU
3 : Modbus ASCII
09-10
Reserved
2 Byte
0x00 0x00
Response:
00
Address
1 Byte
1-2 47
01
Function code
1 Byte
0x46
02
Sub-Function code
1 Byte
0x06
03
Reserved
1 Byte
0x00
04
Baud Rate
1 Byte
0 : OK