M-7026
M-7026 User Manual Rev: 1.5 Date: 2016/03/10
130
2.63 @AAEATCi
Description:
This command is used to enable the alarm function and set the Alarm Type for
a specific Analog Input channel of a specified module.
Syntax:
@AAEATCi[CHKSUM](CR)
@
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
EA
The command to enable the alarm function for the Analog Input
channel
T
The Alarm Type for the Analog Input channel
M: Momentary
L: Latched
Ci
The Analog Input channel where the alarm is to be enabled, zero
based (0-5)
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command
AA
The address of the responding module in hexadecimal format (00 to
FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples:
Command: @01EAMC0
Response: !01
Enables the alarm function for Analog Input channel 0 of module 01 and
sets the Alarm Type to Momentary and returns a response indicating that
the command was successful.
Command: @01RAC0
Response: !011
Reads the status of the alarm for Analog Input channel 0 of module 01
and returns a response indicating that the command was successful and
that the alarm is enabled and the Alarm Type is Momentary.
Command: @01EAMCF
Response: ?01
Attempts to enable the alarm for Analog Input channel 15 of module 01
and set the Alarm Type to Momentary, but returns a response indicating
that command was unsuccessful because the Analog Input channel 15
does not exist.
Related Commands:
Section 2.55 @AACHCi, Section 2.58 @AACLCi, Section 2.61 @AADI,
Summary of Contents for M-7026
Page 8: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 8 1 3 Pin Assignments...
Page 12: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 12 1 5 Block Diagram...
Page 13: ...M 7026 User Manual Rev 1 5 Date 2016 03 10 13 1 6 Application Wiring...
Page 43: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 43 Section 1 8 1 Analog Input Calibration...
Page 47: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 47 Section 5 1 INIT Mode...
Page 90: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 90 Section 5 2 Dual Watchdog Operation...
Page 113: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 113 Section 2 68 AARECi...
Page 127: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 127 Section 2 62 AADODD...
Page 129: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 129 Related Commands Section 2 61 AADI...
Page 141: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 141 Related Commands Section 2 53 AACECi...
Page 180: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 180...
Page 183: ...M 7026 M 7026 User Manual Rev 1 5 Date 2016 03 10 183...