P6
Model Name
Type and Rating
Size A Size B
iWSN-9601-PCT-ME-IP33
Split CT, Max. 400 A
-
-
iWSN-9601-160-ME-IP33
Split CT, 100 A
15.7
29
iWSN-9601-240-ME-IP33
Split CT, 200 A
23.6
45.2
iWSN-9601-360-ME-IP33
Split CT, 400 A
35.7
57.5
6.
Module Installation
7.
Operations
Users can prepare a PC and iWSN-200U (or iWSN-200E) for data collection
of iWSN-9601 series modules.
1.
Configure the RF channel and Group ID of iWSN-200U/E to the same
configuration of the iWSN-9601 series modules.
2.
Set
the Node ID (1 ~ 31),
wiring type and Tx duty, and
finish the wiring connection.
The Node ID must be
unique in a sub-network
(the same RF channel and
group ID). The architecture
might look like as the
right-hand-side figure.
The iWSN-9601 series provide the
IP33 rating enclosure which can effectively
prevent the modules from the influence of
the fire sprinkler systems. Users need to
install the module vertically and screws up
the LED panel cover and connector
protector properly to guarantee the IP33
rating performance.
The iWSN-9601 series modules can only be used
with the specific CTs. Only the model name
iWSN-9601-PCT-ME-IP33 doesn’t include CTs.
Please check the accessories of the product
website or contact to the ICP DAS distributor to
purchase the CTs for this model if necessary.
Different model name provides different size of
CTs, they are described below.
Unit: mm
Vertical
Horizontal