P8 

 

Note

 

1.

 

If  you  need  to  remove  the  terminal  lines,  always  detach  the  CT  before 
removing  the  CT  terminal  lines.  Otherwise  the  CT  may  develop 
open-circuit secondary voltages which may be hazardous to  personnel  or 
damaging to the CT or equipment connected in the secondary circuit. 

2.

 

The external CT’s are fragile, please handle with care. 

3.

 

The  current  input  of  the  iWSN-110X  series  only  supports  the 
factory-attached CT. 

4.

 

To  install  CT’s  correctly,  please  ensure  the  CT  lines  sequences  is  right 
before clip the CT’s onto the power cable of the monitoring equipment. 

5.

 

Please  select  the  appropriate  size  CT  for  different  size  monitoring 
equipment  cables:  power  line  diameter  <Φ24  using  200A  CT,  Φ36  using 
400A CT. 

6.

 

The maximum current value cannot exceed the CT rating.

 

 

Summary of Contents for iWSN-110X Series

Page 1: ...1C016 Module Name Split core CT Module Name Split core CT iWSN 110X PCT ME Without CT iWSN 110X 240 ME 8m 24mm 200A 1 pcs iWSN 110X 160 ME 8m 16mm 100A 1 pcs iWSN 110X 360 ME 8m 36mm 400A 1 pcs Techn...

Page 2: ...on other than electrical power monitoring Product Warranty Customer Support ICP DAS warrants all products free from defects in material and workmanship for a period of one year from the date of shippi...

Page 3: ...horted 3 N A 2 CT Split core CT pin no directionality support measuring and charging function 1 CT Extension bus Instructions Ext_Bus Empty or connect extension module Button Instructions Wake Manual...

Page 4: ...ication parameter Name Instructions F2 Reserved F1 TX Duty RF transmit duty ON OFF Period Pin 5 6 1 sec 10 sec 30 sec 60 sec RF Ch RF Channel ON OFF Ch Pin Ch Pin 1 2 3 4 1 2 3 4 0 8 1 9 2 A 3 B 4 C 5...

Page 5: ...nstructions PA Factory Only GID Group ID ON OFF Group Pin 6 7 0 1 2 3 Node ID ON OFF Node Pin Node Pin 1 2 3 4 5 1 2 3 4 5 0 16 1 17 2 18 3 19 4 20 5 21 6 22 7 23 8 24 9 25 10 26 11 27 12 28 13 29 14...

Page 6: ...ny questions please contact technology support Blink twice Component status is abnormal 1 Please confirm whether the audio line of Ext_Bus is fully inserted and the module is power off And power on af...

Page 7: ...ns for 5 seconds C When power on if STA will light on for 1 second and off this mean boot complete If STA do not be lighted please press Boot for 1 3 seconds and confirm STA will light on for 1 second...

Page 8: ...The external CT s are fragile please handle with care 3 The current input of the iWSN 110X series only supports the factory attached CT 4 To install CT s correctly please ensure the CT lines sequence...

Reviews: