VP-2117 Getting Started,
Apr. 2010, V1.0
3-15
3.12 The connection mode of Fbus
Please refer to CD-ROM: \napdos\isagraf\8000\english_manu\
Dz
user_manual_i_8xx7.pdf
Dz
For detailed ISaGRAF
User‟s Manual.
The Fbus is listed in Chapter 7.
3.13 Setting I-7000 and I-87K Remote I/O by DCON Utility
VP-2117 PAC system can link up to 64 pcs ICP DAS's Remote I/O modules -
Dz
I-7000
dz
and
Dz
I-87K
dz
series Remote I/O modules.
TO DO:
Before linking I-7000 and I-87K modules for Remote I/O, you must use DCON Utility
to pre-set each I-7000 and I-87K remote module to have a unique address (NET-ID),
and set them to the same baud rate as the VP-2117 PAC system.
The DCON Utility is a toolkit that helps user to search the RS-485 I/O network,
easily to configure and test the I/O modules. For DCON Utility program and manual
please reach to
http://www.icpdas.com/products/dcon/introduction.htm
. or
> Products > Software > DCON Utility
NOTE:
1. Make sure the hardware connection is correct.
2. Configure I/O modules with
.
3. Using I-87Kn, please search and configure the modules one by one.
4. I-7000: Connect the INIT* to GND and Power on the module.
I-87K (High Profile): Change the DIP switches of I-87Kn expansion unit or
setup the INIT jumper on I-87K module. Lastly, power on the module.
Step 1: Hardware connection
1. The power supply must be DC power b10V to +30V.
2. Wiring diagram for connecting to I-87K4 + I-87K high profile I/O (one module
for each time)
NOTE:
For I-87K4 I/O module, you have to prepare an I-7520R (RS-232 to RS-485)
converter. For other wiring diagram please refer to
.
ГК
Атлант
Инжиниринг
–
официальный
представитель
в
РФ
и
СНГ
+7(495)109-02-08 [email protected] www.bbrc.ru