I-87211W User Manual
72/93
I-87211W User Manual V2.5, Oct. 2010
Key
Description
OAS
DO Active Status
0: Output value 1 indicates that the relay is active
0:
Output value 0 indicates that the relay is inactive
1: Output value 0 indicates that the relay is active
0:
Output value 1 indicates that the relay is inactive
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.
Related Commands:
Example:
Command: ~01D02
Response: !0102
Sets the DO active status of module 01 and
returns a valid response.
Command: ~01D
Response: !0102
Reads the miscellaneous settings of module 01
and returns 02.
Section 2.22 ~AADVV