I-87211W User Manual
34/93
I-87211W User Manual V2.5, Oct. 2010
2.2 #**
Description:
When the command is received, it allows all modules to read
the data and stores the data for later retrieval.
Syntax:
#**[CHKSUM](CR)
#
Delimiter character
**
Synchronized sampling command
Response:
Valid Command: There is no response with this command. To
access the data, another command, $AA4,
must be sent.
Examples:
Command: #**
Response: No response
Sends the synchronized sampling command to all
modules.
Command: $014
Response: !1060000
Sends a command to read the synchronized data.
The status byte of the response is 1, which means
that it is the first time the synchronized data has
been read after the previous #** command.
Digital Output: 0x06
Summary of Contents for I-87211W
Page 7: ...I 87211W User Manual 7 93 I 87211W User Manual V2 5 Oct 2010 Time Calibration for PACs...
Page 14: ...I 87211W User Manual 14 93 I 87211W User Manual V2 5 Oct 2010 1 4 Hardware...
Page 17: ...I 87211W User Manual 17 93 I 87211W User Manual V2 5 Oct 2010 Block Diagram for the I 87211W...
Page 20: ...I 87211W User Manual 20 93 I 87211W User Manual V2 5 Oct 2010...
Page 23: ...I 87211W User Manual 23 93 I 87211W User Manual V2 5 Oct 2010 1 5 Dimensions...