To calibrate the I-8014W on WinCE and WES unit
Step1
make sure the Differential / Single
Ended
select jumper is in differential
position.
Step2
. Connect your calibration source to
channel 0 of I-8014W by differential
wiring.
Step3
. Plug the I-8014W into the slot of
controller and turn on the controller.
Step4.
Launch
pac_i8014W_Calibration.exe on
controller.
(In the c# demos for I-8014W, see
Demo Programs Location, page 12 and 13
)
Tips & Warnings
Only channel 0 is valid to perform calibration