I-7530A-MR-FD Modbus RTU to CAN
Converter User’s Manual (Version 1.0, 08/2022) ------------- 71
overflow flag
07507
07508
1
Firmware version
07508~07512
07509~07513
5
Module name
07513~07515
07514~07516
3
Manufacturer
The detailed information of the
“Module Status” field is described below.
Status Name
Description
Counter
The unread number of CAN message in the
Normal CAN Message Field of Input Register.
Read Standard
CAN baud rate
configuration
The current baud rate setting of CAN bus.
Please refer to Table 4-2 for more information.
Read user-defined
CAN baud rate
configuration
The current user-defined baud rate setting of
CAN bus. Please refer to Table 4-8 for more
information.
CAN state register
Most significant byte: Reserved.
Least significant byte: register status. Please
refer to Table 4-3 for more information.
CAN Error Counter
Most significant byte: CAN receive error
counter.
Least significant byte: CAN transmit error
counter.
CAN/UART
Overflow flag
Bit 0: CAN overflow flag, 0
Not full, 1
Full.
Bit 1: UART overflow flag, 0
Not full, 1
Full.
Firmware Version
Most significant byte
major field of firmware
version
Least significant byte
minor field of firmware
version
For example, if the responded value is
“01 02”.
That means the firmware version is 1.02.
Module Name
“I-7530A-MR-FD” in ASCII format.
Manufacturer
“ICPDAS” in ASCII format.