Converter User’s Manual (Version 1.0, 08/2022) ------------- 36
Setting steps:
Figure 3-18 CAN filter setting interface
1. Choose to set Standard ID (11bit ID) or Extended ID (29bit ID)
2. Enter the range for the ID filter and press "Add"
3. After pressing "Add", the table below will display the entered ID
4. Finally, click Set to transfer the setting value to I-7530A-MR-FD
Note: The ID entered is a passable ID
Taking Figure 3-17 as an example, the IDs that can be passed are
004~015 and 07F