I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 25
2.1 %AANNTTCCFF
Description
: Set the configuration of module.
Syntax:
%AANNTTCCFF[chk](cr)
% is a delimiter character
AA=2-character HEX module address, from 00 to FF
NN=new AA
TT=input type code, refer to Sec. 1.9
CC=baud rate code, refer to Sec. 1.9
FF=status code, refer to Sec. 1.9
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Response
: valid command
!AA[chk](cr)
invalid command
?AA[chk](cr)
no response
syntax error or communication
error or address error
! is a delimiter character indicating a valid command
? is a delimiter character indicating a invalid command
AA=2-character HEX module address
[chk]=2-character checksum, if checksum disable
no [chk]
(cr)=0x0D
Example
:
command: %0102500600(cr)
response : !02(cr)
command: %0202510600(cr)
response : !02(cr)
Refer to
“
I-7000 Bus Converter User Manual
”
chapter-5
for the following functions:
module status unknown(Sec. 5.1), change address(Sec. 5.2)
change baud rate(Sec. 5.3), checksum enable/disable(Sec. 5.4)
address 01 is configured to a
new address 02, counter
mode
Change to frequency mode
.
7080/7080D