I-7080, I-7080D, I-7080B, I7080BD User Manual (V 2.2) ------------------ 14
1.7 Default Setting
The default setting is given as following:
address=01
baud rate=9600
checksum disable
data=1 start+8 data+1 stop(no parity)
type=50
counter input
alarm=hi alarm on counter 0 & counter 1 (I-7080)
hi/hi-hi alarm on counter 0 (I-7080D)
1.8 Application Notes
1.8.1 Counter/Frequency Input Mode Selection
The counter/frequency input can be selected from isolated
or non-isolated signal. The channel 0 & channel 1 can be
selected separately. There are 4 different input mode given as
following: These four input modes can be used in both of I-7080
& I-7080D.
Input Mode
Command
Channel 0
Channel 1
Input mode 0
$AAB0
Non-isolated
Non-isolated
Input mode 1
$AAB1
Isolated
Isolated
Input mode 2
$AAB2
Non-isolated
Isolated
Input mode 3
$AAB3
Isolated
Non-isolated