                                                    P5 

 

4  

Modbus Address 

 

(0xxxx) DO address:

 

Begin 

address 

Points 

Description 

Bits 

Per 

Point 

Range 

Access 

Type 

0 (0x0) 

1~6 

Digital Output Channels 

0: OFF, 1: ON 

R/W 

32 (0x20) 

Clears the status of all high 

latched DI channels 

1: Clear 

33 (0x21) 

Clears the status of all low 

latched DI channels 

1: Clear 

190 

(0xBE) 

1~6 

Enables frequency 

measurement for all DI 

Channels 

0: Disable 

1: Enable 

(Default: 0) 

R/W/F 

235 

(0xEB) 

1~6 

Sets the Power-on value for 

all DO Channels 

0: OFF, 1: ON 

(Default: 0) 

R/W/F 

267 

(0x10B) 

1~6 

Sets the Safe value for all DO 

Channels 

0: OFF, 1: ON 

(Default: 0) 

R/W/F 

“R”

: Read; 

“W”

: Write;

 

“F”

:

 

Settings are recorded in flash memory by default 

 

 

(1xxxx) DI address:

 

Begin 

address 

Points 

Description 

Bits 

Per 

Point 

Range 

Access 

Type 

(0x0) 

1~6 

Digital Input 

0:Off 
1:On 

32 

(0x20) 

1~6 

Digital latched status (high) 

0:no 

1:latched 

64 

(0x40) 

1~6 

Digital latched status (low) 

0:no 

1:latched 

“R”

: Read 

 

Note 

For detail “DI/DO Modbus Address” information, refer to Section 6.3 Modbus Register Table

 

of user’s manual (

http://ftp.icpdas.com/pub/cd/6000cd/napdos/et2200/document/

).

 

 

 

Summary of Contents for ET-2255U

Page 1: ...5U Quick Start v1 2 Jun 2018 What s in the box Related Information The package includes the following items ET 2255U Module x 1 Quick Start x1 This Document ET 2200 Series Product Page Documentation F...

Page 2: ...your Windows firewall and Anti Virus firewall first else the Search Servers on Chapter 5 may not work Please contact with your system Administrator 2 Connect both the ET 2255U and your PC to the same...

Page 3: ...1 VDC Digital Input Counter Sink Source To other channels 7 5K DI COM DIx To other channels 7 5K DI COM DIx To other channels 7 5K DI COM DIx To other channels 7 5K DI COM DIx Open Close to GND Dry C...

Page 4: ...r Self test A tip for connecting the wire to the connector A tip for removing the wire from the connector 1 Connect the DI0 pin Pin17 to the DO0 pin Pin18 2 Connect the External Power 24V to the DI CO...

Page 5: ...EB 1 6 Sets the Power on value for all DO Channels 1 0 OFF 1 ON Default 0 R W F 267 0x10B 1 6 Sets the Safe value for all DO Channels 1 0 OFF 1 ON Default 0 R W F R Read W Write F Settings are recorde...

Page 6: ...earch Servers to search your ET 2255U 3 Double click your ET 2255U to configure the settings Factory Default Settings of ET 2255U IP Address 192 168 255 1 Subnet Mask 255 255 0 0 Gateway 192 168 0 1 4...

Page 7: ...e ET 2255U is working well with new configuration 2 Click the name of ET 2255U to select it 3 Click the Web button to log in to the web configuration pages Or enter the URL address of the ET 2255U in...

Page 8: ...as com P8 5 In the Home page allows a simple test to be performed to verify the Digital Input and Output functionality 6 In the Digital I O section click the DO0 button to ON Red 7 The corresponding D...

Reviews: