GW-7553-CPM PROFIBUS/CANopen GATEWAY User Manual
(Version 1.00, Apr/2016)
PAGE: 14
LED Name
Status
Description
will flash slowly (flash once about 220ms).
on
Connection error between PROFIBUS master and
slave or PROFIBUS system has not been configured
correctly.
off
Normal operation
PROFIBUS system has been configured correctly
RUN
on
Data exchange mode
Normal operation.
off
GW-7553-CPM module is not in a data exchange
mode.
Figure 10 LED position
2.6 Normal/Setting Dip Switch
There is a dip switch on the back of the GW-7553-CPM module, as shown in Figure
11. The dip switch is used to set the GW-7553-CPM module works in operation mode
or setting mode. In the normal situation, it needs to set the dip switch to the
“
Normal
”
position. In this case, the GW-7553-CPM module can communicate with CANopen
devices, module can communicate with the utility tool and read the information of
CANopen from the module. When the user sets the dip switch to the
“
Setting
”
position, the GW-7553-CPM module can communicate with the utility tool and save
the information of CANopen to module.