Correction Sensor Position
Flange
2x 90 Elbow
Reducer
90 Elbow Downward flow
90 Elbow Downward flow Upward
Ball Valve
Inlet
Outlet
Outlet
Inlet
Outlet
Inlet
Inlet
Outlet
Outlet
Inlet
Outlet
Inlet
10xID
5xID
25xID
5xID
15xID
5xID
40xID
5xID
20xID
5xID
50xID
5xID
Good if NO
Sediment Present
* Maximum % Solids: 10% with particle size not exceeding 0.5 mm cross section or length.
Good if NO Air
Bubbles Present
Preferred Installation if Sediment* or
Air Bubbles may be Present
TI Series Flow Meters measure liquid media only. There should be no air
bubbles and the pipe must always remain full. To ensure accurate flow
measurement the placement of the flow meters needs to be adhered .This
requires a straight run pipe with a minimum number of pipe diameters
distance upstream and downstream of the flow sensor.
Developed Turbulent Flow
Velocity
Profile
Flow
www.iconprocon.com | [email protected] | 905.469.9283
09
Battery Operated
-
Paddle Wheel Flow Meter
TIB SERIES