Icon Process Controls truflo Ultraflo UF500 Instruction Manual Download Page 9

6

6.

System INFO

System INFO:  Display serial number (SN) of the meter. This SN 

 

is   the 

only one assigned to each flow meter

.

 

Set zero: Press 

 

   

  

 ;

 

reset “Zero Point” which was set by the user.

 

Manual Totalizer: The manual totalize

r

 is a separate totalize

r

.  

Press        to start, and press        to stop

.

 It is used for

 isolated

 flow 

measurement and calculation.

Setup Menu – Calibration

Press

 

 

to 

display:

 , Select 2.Calibration, and the

   

n

 

and

 

 to display 4mA 

set point.

Use        and       to set 4mA.
After 4mA is set, press      

  

to move to your 20mA set point. 

Once 20mA is set, press      

 

 to move to next screen.

2.

Set Zero:

 

Press

 ; reset “Zero Point” which was set by the user.

3.

Low flow Cut

: Flow rate below the low flow cutoff value.

ft

ft

Press

1.

Scale factor

Refers to the ratio between 

the 

“actual value”

 

and

 

“reading  value”. For

example, when the measurement is 2.00, and it is indicated at 1.98

 

on the

instrument, the scale factor reading is 2/1.98.

This means that the best scale factor constant is 1.01.

2.

Calibrate

 

&

 20mA

Press

Summary of Contents for truflo Ultraflo UF500

Page 1: ...Ultraflo UF500 Instruction Manual...

Page 2: ......

Page 3: ...Content Product Components 1 Installation and Connection 2 Panel Function 3 Powering On 3 Keypad Functions 3 Display Descriptions 4 Dimensions 8...

Page 4: ...Display Cable Base Bracket Upper Bracket Instruction manual Coupling Agent Instruction Manual F5 1 Notice Thank you for choosing UF 500 Series Flow Meter This instruction manual contains the important...

Page 5: ...rside of the pipe Step3 Slowly remove the protective cover off the sensor Step5 Connect the M cable Step2 Align the upper bracket to the pipe position Using the mounting screws connect the upper and t...

Page 6: ...99 represents that no signal is being detected while 99 represents the GPM Gal 0 F maximum signal strength Keypad functions Follow these guide lines when using the Flow meter keypad Press to enter th...

Page 7: ...onthly Total Yearly Total Press to return to previous menu Display Run time Date Month and Year Net Total Setup Menu Press to display Setup menu The following options are available using the or button...

Page 8: ...available using the or buttons 0 System Unit Press or to choose between Metric English 1 Flow Rate Unit Press or to choose between m3 h LPM GPM 2 Total Unit Press or to choose between m3 L GAL 3 Total...

Page 9: ...Calibration and then and to display 4mA set point Use and to set 4mA After 4mA is set press to move to your 20mA set point Once 20mA is set press to move to next screen 2 Set Zero Press reset Zero Poi...

Page 10: ...cation on the display will be zero This function can prevent the flow meter from reading flow after a pump is shut down but there is still liquid movement in the pipe which would result in a flow tota...

Page 11: ...mm B mm C mm D mm Model min max 25 25 28 5 29 5 36 41 1 5 25 58 58 58 68 78 91 1 5 32 1 5 38 4 5 28 4 5 35 8 5 45 8 15 18 5 24 27 32 1 5 20 1 5 48 1 5 58 8 23 8 5 54 5 64 sales iconprocon com support...

Reviews: