OPERATION

User Manual

WALL-MOUNTING ELECTRONIC THERMOSTATS

 

Read all instructions carefully

DIMENSIONS

WIRING DIAGRAMS

LEGEND

INSTALLATION

2

Advanced programming

Setpoint modification

Depleted batteries signal

Error messages

Auxiliary input configuration

Replace the batteries as soon as 

possible! 

Dispose of batteries

in the appropriate recycling

containers.

Reset

Reset to delete the settings  

you made and reload the  

default values. To reset: 

remove the batteries. 

   Wait until the display goes off. 

2

 Insert the batteries. 

   During the flashing press

   the keys 

 and 

 

   until the display shows  

DEf.

3 sec.

Default values

Heating setpoint  

21 °C

Cooling setpoint  

25 °C

Minimum settable setpoint  - 

L0

2 °C

Maximum settable setpoint - 

Xi

50 °C

Operating mode  

 (heating)

Antifreeze temperature

6 °C

Regulation type

On /Off

Differential

0.3 °C

Auxiliary input DIG

DIG

Password

- - - (deactivated)

“Night reduction” function reduces

the programmed setpoint by 3 °C.

Press for 3 seconds the key to

 to activate (or deactivate, 

if already active) the night reduction.

When the night reduction is active, the

display shows the symbol.  .

Night reduction

AUXILIARY

INPUT

COM

NO

NC

EST

84

28

84

Switch off

Normal operation

Note: in heating mode (winter), if the instrument is off, it adjusts according to the 

antifreeze temperature 

Toff

 in order to prevent the system freezing.

Toff

 can have values from 1 to 50° C or be excluded; in this case any minimum 

temperature is guaranteed.

Occurs in case of probe failure.

In this case the adjustment is inhibited and the relay contacts 

remain in NC-COM position.

Occurs for the following values of measured temperature:

t < 0°C

t >50°C

Modification of the desired 

temperature (setpoint), 

 to increase   

 to decrease

Normal operation

heating on (

   

)

or

3 sec.

3 sec.

19.8

19.9

...

3 sec.

Wall-mounting electronic battery thermostat suitable for temperature regulation 

both in heating and cooling.

It has a configurable auxiliary input for the connection of a temperature probe or 

of an external contact with which to reduce the setpoint by 3°C.

It performs actions of 1B type and is intended to operate in environments with 

pollution degree 2 and overvoltage category III (EN 60730-1).

Code  

 

Description

88P4160199 

 

Battery thermostat with auxiliary input

SAFETY WARNINGS

 

 During product installation and operation it is necessary to observe the 

following instructions:

1)    The instrument must be installed by a qualified person, in strict compliance 

with the connection diagrams.

2)   Do not power or connect the instrument if any part appears to be damaged.

3)    After installation, inaccessibility to the connection terminals without appropriate 

tools must be guaranteed.

4)    The instrument must be installed and activated in compliance with current 

electric systems standards.

5)   Before accessing the connection terminals, verify that the leads are not live.

TECHNICAL SPECIFICATIONS

•   Power supply:

  – 2 alkaline batteries 1.5V (AAA type)

  – battery life: 12 months

  – depleted batteries indication

•   Terminals:

  – 3 terminals for 1.5 mm

2

 cables for output relay 5A / 250 Vac

  – 2   terminals for 1.5 mm

2

 cables for auxiliary input (to connect a temperature 

probe or an external contact to reduce setpoint of 3°C)

•   Operating mode: summer/winter/off (with antifreeze)

•   Password protected lock keypad

•   Type of command:

  – on/off with settable differential (0.1 ÷ 1°C)

  – P8 proportional with 0.8°C band (-0.3 ÷ +0.5°C) and period 8 minutes

  – P15 proportional with 1.5°C band (-0.7 ÷ +0.8°C) and period 15 minutes

•   Measurement precision: ± 0.5 °C

•   Measurement temperature resolution: 0.1 °C

•   Setpoint range: 2°C ÷ +50°C

•   Operating temperature: 0 °C ÷ +50 °C

•   Storage temperature: -10 °C ÷ +65 °C

•   Operating humidity: 20÷90% non condensing

•   Protection degree: IP40

•   Insulation: reinforced among accessible parts (frontal) and all other terminals

During the normal operation the thermostat displays the measured temperature value and the relay status is identified by the symbol

   

(heating)  

or the symbol

   

(cooling).

 REFERENCE STANDARDS

Compliance with Community Directives

2014/35/EU (LVD)

2014/30/EU (EMCD)

is declared with reference to the following harmonized standards:

• EN 60730-2-9

Minimum settable setpoint - 

L0

It’s the minimum value settable as setpoint.

Settable values: 2 ÷ 

HI

Maximum settable setpoint - 

KI

It’s the maximum value settable as setpoint.

Settable values: 

L0

 ÷ 50°C

Operating mode - 

E-I

 if connected to the boiler (heating)

 if connected to a cooling system

Antifreeze temperature - Toff 

- (only in heating)

Minimum temperature maintained with instrument off  (see 

box «Switch off»).

Settable values: 1 ÷ 50°C or --- (excluded function)

Type of command - 

REG

 

- (only in heating)

0

   = on/off with settable differential

P8

   =  proportional with band 0.8°C and period 8 minutes

P15

  = proportional with band 1.5°C and period 15 minutes

Differential - 

d0.3

 - (only on/off regulation)

Differential (or hysteresis) for temperature regulation.

Settable values: 0.1 ÷ 1°C

Input configuration - Est

^

_[

 for one temperature probe connection

-  

DIG

 for connection of an external contact to reduce setpoint 

(see “Auxiliary input configuration”)

Password for keypad lock - 

PAS

Set a value between 001 and 999 to activate the keypad lock.

Set 

---

 to disable the lock.

If the keypad lock is active, pressing one key 

LoC

 appears 

and the password is required. If it’s properly inserted the 

keyboard is unlocked for the next 30 seconds.

88P4160199 has an auxiliary input that can be configured for connection instead 

of:

-  an external remote temperature probe. In this case  the value measured by the 

external probe is used to display and adjust the temperature.

-  an external contact for the set-point temperature reduction.  

Closed external contact allows setpoint reduction of 3 °C  

than the set one. Display shows the symbol  .

For auxiliary input configuration, see “Advanced programming” on this manual.

  

 

“Room temperature” 

field

  

 “Off” 

field

  

 

“Heating activation” 

field

  

 

“Cooling activation” 

field

  

 

“Active night reduction” 

field

   

Key 

“   ” Increases the selected field - active night reduction

   

Key 

“   ” decreases the selected field

•  Install the thermostat at a height of about 1.5 m above the floor, away from 

direct sunlight,  away from doors, windows, heat sources, locations with 

excess or total lack of ventilation.

•   Remove the front shell acting in accordance with the picture on the right.

•   Make the connections by respecting the diagrams described in this manual.

•   Insert the batteries in the compartment

•   Fix the instrument to the wall.

•   Reposition the front shell, by mating first the teeth on the upper side. 

To enter menu Advanced programming keep simultaneously pressed for 3 seconds the

keys 

 and 

 until 

PR

 will appear. 

The items of the menu are displayed in succession. For each item is displayed an identi-

fication abbreviation and its relative blinking value. Use the 

keys 

 and 

 to modify the value. The passage to the 

next parameter occurs after 3 seconds without pressing any key. 

Once all parameters are set the writing 

END

 is displayed and 

the thermostat returns to normal operation saving the effected 

modifications.

60

Remove the front shell

View wheelbase hole

Batteries replacement

• Remove the front shell.

•  Insert the batteries in the appropriate 

compartment (attention to the polarity).

• Reposition the front shell.

press

V3IS00904-011

ICMA S.p.a.

via Garavaglia, 4 - 20012 Cuggiono (MI) - ITALIA   

Tel. +39 02 97249134 / +39 02 97249135 - Fax +39 02 97241550

www.icmaspa.it - e-mail: [email protected]   

12-2018

3 sec.