Networkable Dual Duct VAV Controller
Specification and Installation Instructions
EVCBM14NIT2S-TRL24-TDU-V410-180829-ESL
Page | 1
Controller Models
EVCBM14NIT2S
(Master controller / 2 TRIACs)
EVCS14N
(Slave controller)
TRL Series Thermostat
TRL24
(Room Sensor: Temp)
TRLH24
(Room Sensor: Temp and %RH)
TRLG24
(Room Sensor: Temp and CO
2
)
TRLGH24
(Room Sensor: Temp, %RH and CO
2
)
TDU Series Thermostat
TDU10
(Grey LCD, white enclosure)
TDU40
(Black LCD, black enclosure)
TDU70
(Black LCD, white enclosure)
Description
The EVCB Series is a combination controller and thermostat with
support for networked communications via the BACnet MS/TP or
Modbus protocol. The EVCB Series controller is compatible with both
TRL24 and TDU series thermostats. The Networkable Dual Duct VAV
Controller is designed for simple and accurate control of any variable
air volume box in a number of zone control configurations. Its field
configurable algorithms enable versatile implementation of required
control sequences.
EVCB Series
TRL24 Series
TDU10 / TDU40 / TDU70 Series
Typical Application
Applications
Dual duct
o
Cold and hot duct monitoring
o
Cold and discharge duct monitoring
o
Hot and discharge duct monitoring
o
Pressure independant only
Features
Field configured VAV algorithms, inputs and outputs
Built-in actuator, 70 lb-in
Control external actuators using analog (0-10Vdc, adjustable)
On-board differential pressure sensor
Select direction on analog outputs
Simple air balancing and commissioning via thermostat
Configurable PI (Proportional-Integral) function
Independent, configurable proportional control band and dead
band per ramp
Selectable internal or external temperature sensor (10KΩ)
Activate output with CO
2
sensor from TRLG24/TRLGH24/TDU or
external sensor input
Internal and external temperature sensor calibration
Freeze protection
Removable, raising clamp, non-strip terminals
Operational Features
Backlit LCD with simple icon and text driven menus
Select thermostat’s default display
Network service port via on-board mini USB connector
Manual night setback or no occupancy override
Multi level lockable access menu and setpoint
Selectable Fahrenheit or Celsius scale
3-wire connection to controller and 4 push keys
Network Communication
BACnet MS/TP or Modbus communication port
Select MAC address via DIP switch or via network
Automatic baud rate detection
BACnet MS/TP®
Automatic device instance configuration
Copy & broadcast configuration via thermostat menu or
via BACnet to other controllers
BACnet scheduler
Firmware upgradeable via BACnet
Support COV (change of value)
Modbus
Modbus @ 9600, 19200, 38400 or 57600 bps
RTU Slave, 8 bits (configurable parity and stop bits)
Connects to any Modbus master