Configuration Mode
OFF
PM
1 . Verify the SC5011 is in the
OFF
mode .
Press the
SYS
(left) button until off mode displays .
2 . Remove the cover of the thermostat by gently pulling near one of the
corners at the top of the thermostat .
3 . Press the
CONFIG
button for 1 second while the SC5011 is in
OFF
mode .
To exit configuration mode, press the
CONFIG
switch for 1 second .
Press the up or down button to change settings within each screen .
Down
button
Up
button
Press the right button to advance to the next screen .
Note:
Pressing the
left
button will return you to the previous screen .
Left
button
Right
button
The configuration mode is used to set the SC5011 to match your heating/cooling system . The SC5011
functions with heat pump, air conditioning, gas, oil or electric heat systems .
To configure the SC5011, perform the following steps:
S1 S2 Y
W
O/B
G RC RH C
RESET
CONFIG
RC
RH
FP
CONFIG