16.
Status Indicator Light
(Lt 0, 1, 2, 3)
0 = Status indicator never on
1 = Status indicator on with first stage
2 = Status indicator on with second stage
3 = Status indicator on with third stage
Press the or button to select.
Note:
Red light indicates heating cycle and green light indicates cooling cycle.
Slide the
Mode
switch to
Heat
or
Cool
to exit configuration.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
13.
Room temperature offset
(+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Note:
When not set to 0,
ROOM
will display
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
15.
Filter Check time
(300-800, – – –)
Set Fan Run Time (in hours) when
Check Filter
is displayed or set to – – – to disable.
Press the or button to select.
Note:
After exiting configuration mode, to reset filter counter to zero and clear
filter warning, press the and button simultaneously for 5 seconds.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
14.
Maximum compressor cycles allowed per hour
(-, 2-6)
- = as many as needed, and 2-6 = maximum cycles/hour
Press the or button to select.
Press the
SW6
button to advance to the next screen.